56 Eaton 9395XC UPS 1200kW/1200kVA, 1350kW/1350kVA or 1500kW/1500kVA 164001079—Rev 01
Use the procedures in the following paragraphs to connect the external and battery power wiring.
44..66..11 EExxtteerrnnaall PPoowweerr WWiirriinngg IInnssttaallllaattiioonn
To install wiring to connections:
1. If not previously removed, remove the I/O front panel (see Figure 17 and deadfront panel Figure 21).
NOTE Depending on customer requirements, external power cables can be routed through
either the top or bottom conduit panels.
2. Route the input and output cables through either the top or bottom of the cabinet to the UPS terminals.
See Figure 28 through Figure 31 for wiring access information and terminal locations.
Top Access Wiring. Remove the top conduit plate from the top of the UPS. Identify all conduit
requirements and mark their location. Drill and punch all conduit holes in the top conduit plate prior to
mounting on the UPS. Install the conduit plate and install all conduit runs into the plate. Pull the wiring
through the conduit into the wiring area.
Bottom Access Wiring. Identify all conduit requirements and mark their location. Drill and punch all
conduit holes in the bottom conduit plate prior to mounting on the UPS. Install the conduit plate and install
all conduit runs into the plate. Pull the wiring through conduit into the wiring area.
Retain all panel hardware.
Figure 27. ISBM and ISBM/PM Section Debris Shields
I/O SECTION ISBM/PM SECTION
Debris Shields