Eaton 9395XC UPS 1200kW/1200kVA, 1350kW/1350kVA or 1500kW/1500kVA 164001079—Rev 01 49
Figure 21. I/O and ISBM/PM Electrical Access
Deadfront Panels*
* Behind I/O and ISBM/PM
Front door and front panels (removed).
I/O to ISBM/PM gap
(Temporary for
Electrical Connection Access)
ISBM/PM SECTIONI/O SECTION
3. Unfasten the front door latch and open the ISBM front door open (see Figure 16).
If required for improved access, remove the door as follows:
• Disconnect the cable from the HMI control panel and stow carefully in the cabinet.
• Remove the retaining screw located inside the door at the bottom hinge pivot point, then lift the door
off.
• Retain the hardware for later use.
4. Remove the deadfront panels from the I/O and ISBM/PM sections (see Figure 21).
5. Proceed to paragraph 4.3.2 Electrically Connecting the UPS Sections
UPS System Installation