Eaton 9395XC UPS 1200kW/1200kVA, 1350kW/1350kVA or 1500kW/1500kVA 164001079—Rev 01 49
Figure 21. I/O and ISBM/PM Electrical Access
Deadfront Panels*
* Behind I/O and ISBM/PM
Front door and front panels (removed).
I/O to ISBM/PM gap
(Temporary for
Electrical Connection Access)
ISBM/PM SECTIONI/O SECTION
3. Unfasten the front door latch and open the ISBM front door open (see Figure 16).
If required for improved access, remove the door as follows:
Disconnect the cable from the HMI control panel and stow carefully in the cabinet.
Remove the retaining screw located inside the door at the bottom hinge pivot point, then lift the door
off.
Retain the hardware for later use.
4. Remove the deadfront panels from the I/O and ISBM/PM sections (see Figure 21).
5. Proceed to paragraph 4.3.2 Electrically Connecting the UPS Sections