50 Eaton 9395XC UPS 1200kW/1200kVA, 1350kW/1350kVA or 1500kW/1500kVA 164001079—Rev 01
44..33..22 EElleeccttrriiccaallllyy CCoonnnneeccttiinngg tthhee UUPPSS SSeeccttiioonnss
1. Remove the I/O bottom entry conduit plate and retain the hardware for later use (see Figure 22).
Figure 22. Section Bottom Entry Landing Conduit Plate
Bottom Entry Conduit
Landing Plate
I/O Section
Ground
NOTE AC and DC input inter-cabinet power wiring harnesses are secured in the ISBM/PM to
brackets for shipping in the left side of the ISBM section. The shipping brackets can be
removed and discarded after releasing the power wiring.
2. Disconnect the power wiring harnesses from the ISBM shipping brackets (see Figure 23).
UPS System Installation