Installation
4-4 Eaton 93PM Integrated Battery Cabinet-Small Welded (IBC-SW) Installation Manual P-164000639—Rev 1 www.eaton.com/powerquality
16. The IBC–SW is shipped set up for rear ventilation with a cover plate installed over the ventilation grill on
top of the unit (see Figure 4-3). If top ventilation is required, remove the screws securing the plate at the
top of the unit and install the plate over the rear ventilation grill (see Figure 4-4).
CAUTION
To prevent tipping when rolling the cabinet, push the cabinet from the rear whenever possible.
17. Roll the IBC–SW to the line-up-and-match installation location on the right side of the UPS cabinet making
sure the covers are flush with each other or to the standalone installation location.
18. Secure the IBC–SW in position by lowering the leveling feet until the cabinet is level and locked in place.
19. Locate the top splice bracket shipped with the IBC–SW.
20. Remove the screws along each adjacent cabinet top panel securing the top panels. Retain the hardware
for later use.
21. Install the top splice bracket between the adjacent cabinet and secure the tie strap with retained
hardware.
22. If permanently mounting the IBC–SW, proceed to Step 23; otherwise, proceed to Step 26.
23. Locate the two floor mounting brackets from the parts kit.
24. Using the retained cabinet mounting bolts, install the floor mounting brackets to the front and rear of the
IBC–SW with the angle facing outward.
25. Secure the cabinet to the floor with customer-supplied hardware.
26. If installing more than one IBC–SW, remove the rectangular knockouts on the bottom front sides the
IBC–SWs (see Figure 4-2) and repeat Steps 1 through 25; otherwise, proceed to Step 27. Install additional
IBC–SWs on the right or left side of the first IBC–SW.
27. Proceed to paragraph 4.3.
NOTE Use the leveling feet to level and lock the cabinet in place.
NOTE In standalone configurations, multiple IBC–SWs are installed adjacent to each other,
but separate from the UPS.

Table of Contents

Other manuals for Eaton 93PM

Related product manuals