End of discharge voltage 1.67 VPC to 1.75 VPC, configurable or au-
tomatic (load adaptive)
Charge current Configurable:
8–20 kW units (one UPM)
Configurable 0...25 A:
1…25 A with the 20 kW UPM (at > 80%
load limited to 15 A)
1…18 A with the 15 kW UPM (at > 80%
load limited to 10 A)
8–40 kW units (two UPMs)
Configurable 0...50 A (at > 80% load auto-
matically limited to 30 A)
0… 36 A with the 15 kW UPM (at > 80%
load limited to 20 A)
Note: the maximum charge current is 25 A
per one 20 kW UPM and 18 A per one 15
kW UPM
Battery start option Yes