Setting Description
Signal Input Select signal input name and function or change contact polarity.
Relay Outputs Configure the relay outputs.
Battery test Change the power level and duration for battery test.
Bypass Limits Change the bypass voltage or bypass frequency.
Screen Saver Time-
out
Change the screen saver timeout.
Meters Change the meters format.
Lamp Test Enable the lamp test.
HMI backlight Adjust the backlight brightness.
Control P/W level 1 Change the level 1 password, or remove the password on level 1.
The default value is 1111.
Reset statistics Reset all statistics.
Minimum required
kVa
Change the minimum required kVa.
7.2 Signing in
If the level 1 password is enabled, you need to sign in.
1. Press the lock icon in the top right corner of the screen.
2. Type in your password and press OK.
You are signed in.
3. Press Continue to return to the previous screen.
You have 3 attempts to type in the password. If an incorrect password is given
more than 3 times, you need to wait for 30 minutes before trying again.
To modify the user settings, you need to enter the level 2 password. For the
default passwords, see Section
7.1.4.1
.
7.3 System control instructions
7.3.1 Starting the UPS system in the double conversion mode
The UPS system can consist of a single UPS or several parallel UPSs. UPSs
with their MOB open are not considered as part of the system.
To start the UPS system:
1. Open the UPS front door.
2. Check that the rectifier input switch S1 closed.
3. Check that the battery breaker CB1 is closed.
4. Close the UPS front door.
5. Close the UPS input feeder circuit breaker.