EasyManua.ls Logo

Eaton 93PS-8(20)-20(-C) - Page 37

Eaton 93PS-8(20)-20(-C)
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
X = clearance at the back of the UPS cabinet
Y = clearance at the top of the UPS cabinet
Figure 8. UPS cabinet clearances.
The basic environmental requirements for the operation of the UPS system are
as follows:
Ambient temperature range: from +0 to +40 °C
Recommended operating range: from +20 to +25 °C
Maximum relative humidity: 95%, non-condensing
It is required that ventilation of the UPS room is arranged. Sufficient amount of
air cooling is needed to keep the maximum room temperature rise at the desired
level:
Temperature rise of +5 °C maximum requires the airflow of 600 m
3
per 1 kW
of losses.
Temperature rise of +10 °C maximum requires the airflow of 300 m
3
per 1
kW of losses.
An ambient temperature from +20 °C to +25 °C is recommended to achieve a
long life of the UPS and batteries. The cooling air that enters the UPS must not
exceed +40 °C. Avoid high ambient temperature, moisture, and humidity.
For ventilation requirements, see 93PS heat rejection in Table
7
.
Table 7: Air conditioning or ventilation requirements during full load operation
Heat rejection
(BTU/h x 1,000)
Heat rejection
(kW)
8 kW 1.17 0.3
Eaton 93PS UPS 8–40 kW User's and installation guide
©
Eaton Corporation plc 2016. All rights reserved. Revision: 003 Document ID: P-164000493 37 (104)

Table of Contents

Related product manuals