- the maintenance bypass and the UPS, or
- the maintenance bypass and the rectifier input breaker.
If a bypass input breaker is installed in the maintenance bypass and a single-
feed UPS is being installed., a single feed to the maintenance bypass is
acceptable for supplying both the UPS and the bypass.
An additional single feed kit (P-103002165 KIT 93PS-20 SINGLE FEED) is
available for the 8–20 kW cabinet. Maximum conductor cross section of the
single feed is 35 mm
2
.
When you plan and perform the installation, read and understand the following
notes:
Refer to the national and local electrical codes for acceptable external wiring
practices.
To allow for future kVA upgrades (software and/or hardware), consider using
conductors that are sized for the full bypass rating of the UPS.
Material and labor for external wiring requirements must be provided by
designated personnel.
For external wiring, use copper cable rated for 70 °C at minimum. See the
appropriate information in Table
8
. Cable sizes are based on using the
specified breakers.
If cables are run in an ambient temperature greater than 30 °C, higher
temperature cable and/or larger size cable may be necessary.
The bypass feed into this equipment uses four cables. The rectifier feed into
this equipment uses three or four cables. The phases must be symmetrical
about ground (from a Wye source) for proper equipment operation.
If the load requires a neutral, a bypass source neutral must be provided. If
the load does not require a neutral and there is no neutral conductor
connected at the bypass input, a neutral must be installed to source star
point.
A readily accessible disconnect device must be incorporated in all fixed input
wiring.
WARNING
Do not disconnect the bypass neutral without disconnecting the bypass
phases at the same time.
Table 8: Minimum recommended multi-core cable and fuse sizes for rectifier and bypass
input and UPS output cables
UPS rating (kW) 8 10 15 20 30 40
Cable [mm
2
]* 4*2.5 4*4 4*10 4*10 4*16 4*25
Rectifier fuse [A] 20 20 32 40 63 80
Bypass fuse [A] 20 20 32 40 63 80
Eaton 93PS UPS 8–40 kW User's and installation guide
©
Eaton Corporation plc 2016. All rights reserved. Revision: 003 Document ID: P-164000493 39 (104)