1 X1: rectifier input, N 12 X3: UPS output, L3
2 X1: rectifier input L1 13 X4: external battery cable + **
3 X1: rectifier input L2 14 X4: external battery cable – ***
4 X1: rectifier input L3 15 TB20: external battery trip
5 X2: bypass input, N 16 TB21: external battery trip *
6 X2, bypass input, L1 17 PE
7 X2: bypass input L2 18 X4:1: external battery cable + *
8 X2, bypass input L3 19 X4:2: external battery cable - *
9 X3: UPS output, N * Only in models with the separate battery
option
10 X3: UPS output, L1 ** X4:3 in models with the separate battery
option
11 X3: UPS output, L2 *** X4:4 in models with the separate battery
option
For the external separate battery option, there are separate terminals for both
battery banks (cabinets). These terminals replace terminals 5 and 10 shown in
Figure
11
.
Note: External overcurrent protection is not provided by this product, but is
required by codes. Refer to Table
8
for wiring requirements. If a lockable
output disconnect is required, it must be supplied by the user.
Table 11: UPS power cable terminal torques
UPS frame Function Tightening torque
93PS 20 kW X1, X2, X3: L1, L2, L3, N 1.6
X4: battery +/- 3.0
PE (ground) 3.0
93PS 40 kW X1, X2, X3: L1, L2, L3, N 6.0
X4: battery +/- 6.0
PE (ground) 3.0
CAUTION
To reduce the risk of a fire, connect only to a circuit that is provided with
maximum input circuit breaker current ratings from Table
10
in accordance
with the national and local installation rules.
The line-to-line unbalanced output capability of the UPS is limited only by the full
load per phase current values for AC output to critical load shown in Table
10
.
The recommended line-to-line load unbalance is 50% or less.
Eaton 93PS UPS 8–40 kW
User's and installation guide
©
Eaton Corporation plc 2016. All rights reserved. Revision: 003 Document ID: P-164000493 44 (104)