SPECIFICATIONS
Eaton 9910 UPS and EBM User's Guide S P-164000005 Rev 2
56
Table 13. Environmental and Safety
9910-E35 and 9910-E66 9910-E36 and 9910-E67
Operating Temperature 0°C to 40°C (32°F to 104°F)
Optimal battery performance: 25°C (77°F)
Storage Temperature -15°C to 45°C (5°F to 113°F)
Transit Temperature -15°C to 60°C (5°F to 140°F) for 24 hours
Relative Humidity 0–95% noncondensing
Operating Altitude Up to 3,048 meters (10,000 ft) above sea level
Transit Altitude Up to 15,240 meters (50,000 ft) above sea level
Audible Noise at
1 meter for >80% Load
Less than 55 dBA Normal mode / Bypass mode
Less than 55 dBA Battery mode
Surge Suppression ANSI/IEEE C62.41; 1991 Category B3
Safety Conformance UL 1778 4th edition, CSA C22.2, No. 107.3-05 Second Edition;
IEC 62040-1-1 and IEC/EN 60950-1
Agency Markings cULus, TUV-CB, NOM, FCC, ICES 9910-E36: cULus, TUV-CB, GOST, C-Tick, CE,
FCC, ICES, KC
9910-E67: TUV-CB, C-Tick, CE, FCC, ICES
EMC (Class A) IEC 62040-2, FCC Part 15, ICES-003, VCCI IEC 62040-2, FCC Part 15, ICES-003
Table 14. Battery
3000 VA Models 6000 VA Models
UPS Configuration (8) 12V, 9 Ah internal batteries (18) 12V, 9 Ah internal batteries
EBM Configuration (8) 12V, 9 Ah (18) 12V, 9 Ah
Type Sealed, maintenance‐free, valve‐regulated, lead‐acid
Monitoring Advanced monitoring for earlier failure detection and warning
Charging (at nominal
line voltage after 50%
load discharge)
Internal battery: 4 hours to 90% usable
capacity
Internal battery: 8 hours to 90% usable
capacity
External battery: 16 hours to 90% usable capacity
Runtime
[for fully charged
batteries at 25°C (77°F)]
Internal Batteries Only:
Full load: 5 min Half load: 14 min
With EBM:
Full load: 23 min Half load: 50 min
Internal Batteries Only:
Full load: 5.5 min Half load: 15 min
With EBM:
Full load: 15 min Half load: 40 min
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.