Force Restart
[Enabled] [Disabled]
[Delay] [10s] ... [180s]
If the main power supply is recovered during the
shutdown sequence:
If Force Restart is set to [Enabled], the
shutdown sequence will be completed and the
UPS will be restarted after 10 seconds.
If Force Restart is set to [Disabled], the
shutdown sequence will not be completed and
the UPS will remain operational.
[Enabled]
[10s]
Low Energy
Consumption
Mode
[Enabled] [Disabled]
[Timing] [1min] ... [15min]
[Load Capacity] [100W] ... [1000W]
If Low Energy Consumption mode is set to
[Enabled], the UPS will shut down when the
load is less than the set load and the battery
standby time is less than the set value.
[Disabled]
[5min]
[100W]
Hibernate Mode
[Enabled] [Disabled]
[Timing] [10min] ... [120min]
If the Hibernate mode is set to [Disabled], the
LCD and communication will be turned off
immediately after the UPS is powered off.
If the Hibernate mode is set to [Enabled], the
LCD and communication will remain operational
for 90 minutes after the UPS is powered off.
[Enabled]
[90min]
Input Cable
Detection
[Enabled] [Disabled]
Avoids the case where the UPS is powered on
with phase and neutral swapped.
[Disabled]
Shutdown
Warning
[Enabled] [Disabled]
If Shutdown Warning is set to [Enabled], a
dialog box will pop up when the user presses
the [On/Off] button, asking the user to confirm
the action before the UPS is powered off.
[Disabled]
Battery Settings
Auto Battery
Detection
In the ABM Charge mode:
[No Self-test] [Every ABM Cycle]
[Every ABM Cycle]
In Constant Voltage Charge mode:
[No Self-test] [Daily] [Weekly] [Monthly]
[Weekly]
Battery Low
[Capacity] [0%] ... [100%]
[Remaining Time] [0min] ... [60min]
This alarm will be triggered when the set battery
capacity or the set remaining discharge time is
reached.
[0%]
[3min]
Battery
Capacity at
Restart
[0%] ...[100%]
The UPS will be automatically restarted only
when the battery capacity reaches the set
value.
[0%]
Charge Mode
[ABM] [Constant Voltage Charge]
[ABM]
External Battery
[Auto Detection] [EBM Settings] [Battery
Capacity Settings]
[Auto Detection]
With standard EBM,
the UPS will
automatically detect
the number of
connected EBMs.