EasyManua.ls Logo

Eaton 9PX 1000i - Page 63

Eaton 9PX 1000i
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Discharge
Protection
[Yes] [No]
If it is set to [Yes], the UPS will automatically
adjust the battery voltage threshold at the end
of battery discharge to prevent the battery from
deep discharge.
It set to [No], it will void the warranty.
[Yes]
Communication
Settings
Input Signal
[ROO] [RPO] [DB9-4]
Parameters of the input signal (function, delay,
and active level) can be set. Its function is
implemented through an external contact point
or the RS232 port.
ROO port:
- [Function]: [No] [ROO] [RPO] [Generate
Alarm] [Force Bypass] [Connect Generator]
[Remote Power Off]
[No]
- [Delay]: [0s] … [999s]
[0s]
- [Effective Time]: [On] [Off]
[Off]
RPO port:
- [Function]: [No] [ROO] [RPO] [Generate
Alarm] [Force Bypass] [Connect Generator]
[Remote Power Off]
[No]
- [Delay]: [0s] … [999s]
[0s]
- [Effective Time]: [On] [Off]
[On]
DB9-4 port:
- [Function]: [No] [ROO] [RPO] [Generate
Alarm] [Force Bypass] [Connect Generator]
[Remote Power Off]
[No]
- [Delay]: [0s] … [999s]
[0s]
- [Effective Time]: [High] [Low]:
[High]
Communication
Settings
Output Signal
[Switch Output] [DB9-1] [DB9-7] [DB9-8]
Sets the output signal parameters at the
occurrence of an event or fault through an
external contact point or the RS232 port.
- [Switch Output]: [Battery Mode ] [Low Battery
Voltage] [Battery Fault] [Bypass] [UPS Normal]
[Load Protected] [UPS with Output] [General
Alarm] [External Charger] [Overload Alarm]
[Switch Output]:
[Bypass]
- [DB9-1]: [Battery Mode ] [Low Battery Voltage]
[Battery Fault] [Bypass] [UPS Normal] [Load
Protected] [UPS with Output] [General Alarm]
[External Charger] [Overload Alarm]
[DB9-1]: [Low Battery
Voltage]
- [DB9-7]: [Battery Mode ] [Low Battery Voltage]
[Battery Fault] [Bypass] [UPS Normal] [Load
Protected] [UPS with Output] [General Alarm]
[External Charger] [Overload Alarm]
[DB9-7]: [UPS
Normal]
- [DB9-8]: [Battery Mode ] [Low Battery Voltage]
[Battery Fault] [Bypass] [UPS Normal] [Load
Protected] [UPS with Output] [General Alarm]
[External Charger] [Overload Alarm]
[DB9-8]: [Battery
Mode]
Remote
Command
[Enabled] [Disabled]
If Remote Command is set to [Enabled], the
Shutdown or restart command from the
software will be allowed to be executed.
[Enabled]

Related product manuals