[Yes] [No] 
If it is set to [Yes], the UPS will automatically 
adjust the battery voltage threshold at the end 
of battery discharge to prevent the battery from 
deep discharge. 
It set to [No], it will void the warranty. 
[ROO] [RPO] [DB9-4] 
Parameters of the input signal (function, delay, 
and active level) can be set. Its function is 
implemented through an external contact point 
or the RS232 port. 
- [Function]: [No] [ROO] [RPO] [Generate 
Alarm] [Force Bypass] [Connect Generator] 
[Remote Power Off] 
- [Effective Time]: [On] [Off] 
- [Function]: [No] [ROO] [RPO] [Generate 
Alarm] [Force Bypass] [Connect Generator] 
[Remote Power Off] 
- [Effective Time]: [On] [Off] 
- [Function]: [No] [ROO] [RPO] [Generate 
Alarm] [Force Bypass] [Connect Generator] 
[Remote Power Off] 
- [Effective Time]: [High] [Low]: 
[Switch Output] [DB9-1] [DB9-7] [DB9-8] 
Sets the output signal parameters at the 
occurrence of an event or fault through an 
external contact point or the RS232 port. 
- [Switch Output]: [Battery Mode ] [Low Battery 
Voltage] [Battery Fault] [Bypass] [UPS Normal] 
[Load Protected] [UPS with Output] [General 
Alarm] [External Charger] [Overload Alarm] 
[Switch Output]: 
[Bypass] 
- [DB9-1]: [Battery Mode ] [Low Battery Voltage] 
[Battery Fault] [Bypass] [UPS Normal] [Load 
Protected] [UPS with Output] [General Alarm] 
[External Charger] [Overload Alarm] 
[DB9-1]: [Low Battery 
Voltage] 
- [DB9-7]: [Battery Mode ] [Low Battery Voltage] 
[Battery Fault] [Bypass] [UPS Normal] [Load 
Protected] [UPS with Output] [General Alarm] 
[External Charger] [Overload Alarm] 
- [DB9-8]: [Battery Mode ] [Low Battery Voltage] 
[Battery Fault] [Bypass] [UPS Normal] [Load 
Protected] [UPS with Output] [General Alarm] 
[External Charger] [Overload Alarm] 
[Enabled] [Disabled] 
If Remote Command is set to [Enabled], the 
Shutdown or restart command from the 
software will be allowed to be executed.