44 Eaton 9PX Lithium-Ion User Guide P-164001006—Rev 02
Table 14. Environmental and Safety (Continued)
1 kV Ethernet
IEC 61000-4-6, (Electromagnetic field): 10 V
IEC 61000-4-8, (Conducted magnetic field): 30 A/m
* for output cable < 10m.
Agency Markings* CE / cULus / NOM / Energy Star / BSMI
Operating Temperatures
0 to 40°C (32 to 104°F) in Online mode, with linear derating for
altitude
Note: thermal protection switches load to Bypass in case of
overheating.
Storage Temperatures
0 to 40°C (32 to 104°F) with batteries
-25 to 55°C (-13 to 130°F) without batteries
Transit Temperature
-25 to 55°C (-13 to 130°F)
Relative Humidity 0 to 96% no condensing
Operating Altitude Up to 3,000 meters (9,843 ft) above sea level, no derating for
35°c (95°F) room temperature
Transit Altitude
Up to 10,000 meters (32,808 ft) above sea level
Audible Noise
< 47 dBA at 1 meter typical for 2K et 3K models
< 40 dBA at 1 meter typical for 70, 1K et 1K5 models
Table 15. Battery
Internal Batteries EBM
Rack / Tower configuration 1500VA: 48Vdc
2200VA: 72Vdc
3000VA: 72Vdc
9PXEBM48RT: 48Vdc
9PXEBM72RT: 72Vdc
Type
Lithium Iron Phosphate (LFP) battery module
Lithium-Ion float service life 8 years /25°C
Monitoring
Integrated battery management system (BMS) for temperature regulation and life
cycle monitoring.
EBM Battery Cable Length 350 mm / 13.78 in
Model Specifications