4.3 What to do When Re-Enabling Zones with
Latching Detectors
Before re-enabling any zone that has latching detectors,
a walk round of the zone in question should be carried out
to check that all detectors and manual call points are not
indicating a fi re condition.
If there are no detectors or manual call points showing the
re condition then the zone can be re-enabled at the panel.
If there are detectors or manual call points showing the fi re
condition then the panel should be reset to clear the fi re
condition before the zone is re-enabled.
FAILURE TO FOLLOW THE INSTRUCTIONS ABOVE
WILL RESULT IN THE PANEL ENTERING A FULL ALARM
CONDITION WHICH WILL EVACUATE THE SITE AND
ACTIVATE ANY OTHER EQUIPMENT ATTACHED TO THE
FIRE ALARM SYSTEM.
4. What to Do Instructions
4.1 What to do in the Event of a Fire Alarm
Condition
CARRY OUT THE PREMISES DEFINED FIRE
EVACUATION PROCEDURES
When it is safe to do so silence the fi re alarm devices and
reset the system.
Note the time the fi re alarm occurred and log the fi re
event in the log book.
If the fi re alarm was a false activation (i.e. there was no
re) then this should be reported to the service company
so appropriate corrective actions can be undertaken.
IT IS THE RESPONSIBILITY OF THE PREMISES
MANAGEMENT TO DEFINE THE FIRE EVACUATION
PROCEDURES AND ENSURE THAT ALL RELEVANT USERS
ARE TRAINED AND THAT FIRE DRILLS ARE PEFORMED.
IT IS ALSO THE RESPONSIBILITY OF THE PREMISES
MANAGEMENT TO ENSURE THAT THERE IS NOTHING
THAT CAN IMPEDE THE OPERATION OF THE FIRE
SYSTEM AND PREVENT ANY OBSTRUCTIONS FROM
BLOCKING THE FIRE DETECTION DEVICES OR MANUAL
CALL POINTS.
4.2 What to do in the Event of a Fault Condition
Note the indications on the front of the panel (refer to
section 8 for more details).
Note the time the fault was noticed and log the fault event
in the log book.
Notify the service company of the fault condition.
What to Do Instructions
6
IMPORTANT
WARNING
March 2016 www.eaton.com
EATON BiWire Flexi User Manual (PR215-216-519-03 15-03-16, PINSTFLEXIUSER)