Operating Instructions
8
6. Operating Instructions
6.1 Multi-Function Buttons
The numerical value in the centre of the button is used to
enter access codes for level 2 and 3.
If the text in the centre of the button appears above a line
(or there is no line) then this function is applicable at access
level 2. If the text in the c entre of the button appears below
a line then this function is applicable at access level 3.
The text above button 3 indicates that this button is the
“Select” button during “Disable/Enable” and “Individual
Zone Test” functions.
6.2 Silence Fire Alarm Devices
• This function is only available at access level 2 and when
the alarms are sounding.
• Enter the access code 3112.
• Press the “Silence/Sound Alarms” button.
• Only the fi re alarm devices will stop sounding, the panel
buzzer will continue sounding.
• This function will immediately exit back to Access Level 1.
6.3 Sound Fire Alarm Devices
• This function is only available at access level 2 and when
the alarms are silent.
• Enter the access code 3112.
• Press the “Silence/Sound Alarms” button.
• Only the General Fire indicator will be lit, the panel buzzer
will sound a continuous tone and all fi re alarm devices will
sound.
• This function will immediately exit back to Access Level 1.
6.4 Reset System
• This function is only available at access level 2.
• Enter the access code 3112.
• Press the “Reset” button.
• This will stop all fire alarm devices sounding, will stop the
panel buzzer and will reset the panel.
• The panel will return to the normal condition after
completing the indicator test routine which turns each
indicator on in turn and then turns them off in turn.
Note: When performing a reset, any test cases will be
cleared
March 2016 www.eaton.com
EATON BiWire Flexi User Manual (PR215-216-519-02 11-01-16, PINSTFLEXIUSER)
EATON BiWire Flexi User Manual (PR215-216-519-02 11-01-16, PINSTFLEXIUSER)
EATON BiWire Flexi User Manual (PR215-216-519-03 15-03-16, PINSTFLEXIUSER)