23
User Manual MN04200002E
Effective January 2016
C441 Ethernet module user manual
(C441R, C441T, C441U, C441V)
EATON www.eaton.com
Table 31. Overload Object Instance Attributes (Cont.)
Attrib NV Access
Data
Type Name Description
113 NV Set/Get UINT Motor Fault
Number of
Restarts
Motor Fault Number of Attempts:
0: Manual
1-4
5: Automatic
114 NV Set/Get UINT Run
Transition
Time
Run Transition Time (sec)
115 NV Set/Get UINT Run
Transition
Percent
Run Transition % of FLA (%)
116 NV Set/Get UINT Ground
Fault Trip
Mode
Ground Fault Trip Mode
0 - Trip on Ground Fault
1 - Alarm No Trip
117 NV Set/Get UINT Ground
Fault Trip
Delay
Ground Fault Pickup Delay (sec)
118 NV Set/Get UINT Ground
Fault Pick-
up Level
Ground Fault Pick-up Level (x0.01A)
119 NV Set/Get UINT Current
Unbalance
Trip Delay
Current Unbalance Trip Delay (sec)
120 NV Set/Get UINT Current
Unbalance
Pick-up
Level
Current Unbalance Pick-up Level (%)
121 NV Set/Get UINT Jam Trip
Delay
Jam Trip Delay (sec)
122 NV Set/Get UINT Jam Pick-
up Level
Jam Pick-up Level (%)
123 NV Set/Get UINT Current
Phase Loss
Trip Delay
Pickup Delay for Current Phase Loss
(sec)
124 NV Set/Get UINT High KW
Trip Time
High Power Trip Delay (sec)
125 NV Set/Get UINT High KW
Trip limit
High Power Pick-up Level (x0.01kW)
126 NV Set/Get UINT Low Power
Trip Delay
Low Power Trip Delay (sec)
127 NV Set/Get UINT Low Power
Pick-up
Level
Low Power Pick-up Level (x0.01kW)
128 NV Set/Get UINT Under
Current Trip
Delay
Under Current Trip Delay (sec)
129 NV Set/Get UINT Under
Current
Pick-up
Level
Under Current Pick-up Level (%)
130 NV Set/Get UINT Overload
Reset
Overload Reset Mode
0: Manual Reset
1: Apply Motor Fault Reset Delay and
Number of Attempts
131 NV Set/Get UINT Load Fault
Reset
Delay Calc
Load Fault Reset Delay Calculator
Enable.
Value = Description
0 = Disable (default)
1 = Enabled
132
NV Set/Get BOOL Overload
on Start
Enable
0 = Disable
1 = Enable
133
NV Set/Get BOOL GF on Start
Enable
0 = Disable
1 = Enable
Supported by CP and HVR only.
Voltage Monitor Object
Class 147 (0x93):
Instance Count: 1
Instance List: 1
Table 32.
Voltag
e Monitor Object Instance Attributes
Attrib NV Access
Data
Type Name Description
1 V Get UINT Voltage L1-L2 Phase A RMS Voltage L1-L2 (V)
2 V Get UINT Voltage L2-L3 Phase B RMS Voltage L2-L3 (V)
3 V Get UINT Voltage L3-L1 Phase C RMS Voltage L3-L1 (V)
4 V Get UINT Voltage Average Average RMS Voltage (V)
5 V Get UINT Voltage
Unbalance
Percentage
Max Deviation from Average
Voltage Divided by Average
Voltage (%)
6 V Get UINT Line Frequency Line Frequency (x0.01Hz)
7 NV Set/Get UINT Voltage Faults
Trip Mode
Voltage Faults Trip Mode
0 - Trip On Supply Fault
1: Alarm-no-Trip (Inhibit Start)
8 NV Set/Get UINT Under Voltage
Pick-up Level
Under Voltage Pick-up Level (V)
9 NV Set/Get UINT Under Voltage
Trip Delay
Under Voltage Trip Delay (sec)
10 NV Set/Get UINT Over Voltage
Pick-up Level
Over Voltage Pick-up Level (V)
11 NV Set/Get UINT Over Voltage Trip
Delay
Over Voltage Trip Delay (sec)
12 NV Set/Get UINT Voltage
Unbalance
Pick-up Level
Voltage Unbalance Pick-up Level
(%)
13 NV Set/Get UINT Voltage
Unbalance
Trip Delay
Voltage Unbalance Run Delay (sec)
14 NV Set/Get UINT Phase Order Phase Order
- 0 (Trip Disabled)
- 1 ACB
- 2 ABC
15 NV Set/Get UINT Supply Fault
Hold-off Time
Restart Delay (sec)
16 V Get UINT Remaining Rapid
Cycling Restart
Delay
Supply Fault - Time to Restart (sec)
100
NV Set/Get UINT Wire Config 0 = Three-phase
1 = Single-phase voltage and
current
2 = Three-phase current only
101
NV Set/Get UINT PT Ratio Indicates a PT ratio:120 step-down
Range = 0 to 8000, 0 indicates no
PT connection
TCP/IP Interface Object
Class 245 (0xF5):
Instance Count: 1
Instance List: 1
Table 33. Object Attributes
Attrib NV Access
Data
Type Name Description
13 NV Set/Get UINT Encapsulation
Inactivity
Timeout
Number of seconds of inactivity
before TCP connection is closed