EasyManua.ls Logo

Eaton C441R - 6.3 EtherNet;IP Object Model for C440 Overload Relay

Eaton C441R
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24
User Manual MN04200002E
Effective January 2016
C441 Ethernet module user manual
(C441R, C441T, C441U, C441V)
EATON www.eaton.com
6.3 EtherNet/IP Object Model for C440 Overload Relay
When the Ethernet module is connected to a C440 overload relay,
the presented object model is compliant with the ODVA Motor
Overload device profile (type: 0x3).
Full Profile for C440
The table below shows the supported classes of the Ethernet
Module when connected to an C440 overload relay.
Class Object
# of
Instances Description
0x01
(hex)
Identity 1 Provides module identity object: See details below.
0x02 Message
Router
1 Internal object implemented per ODVA specifica-
tion
0x04 Assembly
Object
5 Binds attributes from multiple objects for access
with a single Implicit (I/O) connection. See details
below.
0x06 Connection
Manager
1 Internal object supporting connection management.
Implemented per ODVA specification.
0x08 Discrete
Input Point
4 Status information for the discrete Inputs. See
details in previous section.
0x09 Discrete
Output
Point
2 Status and control for the discrete Outputs. See
details In previous section.
0x29 Control
Supervisor
1 Motor control functions. See details in previous
section.
0x2C Overload 1 Motor overload protection. See details below.
0xF5 TCP/IP
Interface
1 Information about the TCP/IP Interface.
Implemented per ODVA specification.
0xF6 Ethernet
Link
2 Ethernet link object for each of the 2 Ethernet ports
on the device. Implemented per ODVA specifica-
tion.
Object Details
Class 1 (0x01): Identity Object
Instance Count: 1
Instance List: 1
Table 34. C440 Identity Object Instance Attributes
Attrib NV Access
Data
Type Name Description
1 V Get UINT CIP
Vendor ID
ODVA assigned Vendor Identification
number.
2 V Get UINT CIP
Device
Type
CIP defined general product type.
3 V Get UINT Product
Code
Vendor Product Code
4 V Get UINT Firmware
Rev
Com Adapter Firmware Rev.
5 V Get WORD Device
Status
This attribute represents the current
status of the entire devices. Its value
changes as the state of the device
changes.
Bit = Definition
0 = Owned. True indicates the device
has an owner.
2 = Configured. True indicates the
application of the device has been con-
figured to do something different than
out of box default. Does not include
communication configuration.
4-7 = Extended Device Status.
8 = Minor Recoverable Fault. True
indicates the device detected a prob-
lem with itself, which is thought to be
recoverable.
9 = Minor Unrecoverable Fault. True
indicates the device detected a prob-
lem with itself, which is thought to be
unrecoverable.
10 = Major Recoverable Fault. True
indicates the device detected a
problem with itself causing a “Major
Recoverable Fault” state.
11 = Major Unrecoverable Fault.
True indicates the device detected a
problem with itself causing a “Major
Unrecoverable Fault” state.
6 NV Set/Get UDINT Serial
Number
32 bit Com Adapter Device Serial
Number.
7 V Get SHORT_
STRING
Product
Name
ASCII product name.
8 V Get USINT Device
State
Present state of the device.
Value = Definition
0 = Nonexistent
1 = Device Self Testing
2 = Standby
3 = Operational
4 = Major Recoverable Fault
5 = Major Unrecoverable Fault
255 = Default for Get Attributes All.
176 NV Set/Get SHORT_
STRING
Assigned
Name
User defined ASCII name.
177 V Get UINT C441
DSP FW
Version
C441 DSP Firmware Version
178 V Get UINT UI
Firmware
Version
User Interface Firmware Version
179 NV Set/Get UINT C441
Unit ID
Unit ID
0x00BA (186) - C441BA
0x00BB (187) - C441BB
0x00CA (202) - C441CA
0x00CB (203) - C441CB
0x00DA (218) - C441DA
0x00DB (219) - C441DB
0x00EA (234) - C4410109(x)
0x00EB (235) - C4410590(x)