Table 101. Register Definition for the S611 Soft Starter (Cont.)
Start
Coil Register
Read/
Write Name Description (Units)
- 3000 R/W Modbus
Consumption
List
The Production and consumption
Registers can be used to create custom
Modbus interface ranges. An example:
If field inputs register address 0 is put
into the first slot of the production
list, the field inputs register value will
be available in the first slot of the
Modbus Production Data Register range.
Production data is data provided by the
device and Consumption data is for
data provided (written) to the device.
Note that the values must be Modbus
Register Address (i.e., Register
Number - 1) not Register Number.
- 4000 R/W Modbus
Consumption
Data
-
7.5 Register Definitions for S811+ Soft Starter
Table 102. Register Definitions for S811+ Soft Starter
Start
Coil Register
Read/
Write Name Description (Units)
1 1 R Field Inputs A bitfield representing the input points.
Bit = Description
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
- 2 R Control
Voltage
Adapter source voltage. ( mV )
- 3 R Ambient
Temperature
Device ambient temperature as mea-
sured from the PCB. ( °C )
- 4 R/W Max Board
Temperature
The maximum board temperature experi-
enced since manufacturing. ( °C )
65 5 R Dip Switch
Value
A bit field representing the present state
of the dip switches.
- 6 R Configuration
CRC
A CRC value calculated over the non-
volatile data present.
- 7 R/W Serial Number 32bit Com Adapter Device Serial
Number.
- 9 R Firmware Rev Com Adapter Firmware Rev.
- 11 R/W Hardware Rev Com Adapter Hardware Rev.
1601 101 R/W Field Relay
Outputs
Warning: changing this value may cause
the output relay(s) to change state.
A bitfield representing the output points.
Bit = Description
0 = Output 1
1 = Output 2
Value 0x00: Output 1 Off, Output 2 Off
Value 0x01: Output 1 On, Output 2 Off
Value 0x02: Output 1 Off, Output 2 On
Value 0x03: Output 1 On, Output 2 On
- 102 R/W Field Inputs
Debounce
Array of debounce values. A debounce
value exists for each input. The
debounce applies to both rising and
falling edge.
Web interface setting examples (comma
separated values):
10,10,10,10 change all four debounce
values to 10 msec;
15,20 changes the first two debounce
values to 15 msec and 20 msec and
leaves the rest unchanged;
,,,30 changes the last debounce value to
30 and leaves the first three unchanged
( milliseconds )
- 110 R/W Modbus TCP
Com Timeout
Communication timeout for Modbus TCP.
0 = Disable. ( milliseconds )
1761 111 R/W Field Relay
Fault Action
When a communication fault occurs
the relays can execute two types of
behavior. The behavior is selected on a
per bit basis.
Bit = Description
0 = Relay 1
1 = Relay 2
Bit Value = Description
0 = Apply Fault Value
1 = No Change
1777 112 R/W Field Relay
Fault State
Communication fault value to be
applied. A bitfield where each bit
defines an output point.
Bit Value = Description
0 = Turn Relay Off
1 = Turn Relay On