C441 Ethernet module user manual
(C441R, C441T, C441U, C441V)
EATON www.eaton.com
Table 102. Register Definitions for S811+ Soft Starter (Cont.)
Start
Coil Register
Read/
Write Name Description (Units)
1793 113 R/W Field Relay
Idle Action
When a communication idle state occurs
the relays can execute two types of
behavior. The behavior is selected on a
per bit basis.
Bit = Description
0 = Relay 1
1 = Relay 2
Bit Value = Description
0 = Apply Idle Value
1 = No Change
1809 114 R/W Field Relay
Idle State
Communication idle value to be applied.
A bitfield where each bit defines an
output point.
Bit Value = Description
0 = Turn Relay Off
1 = Turn Relay On
- 130 R Eth Port 1
Speed Actual
Actual Ethernet link speed. ( Mbs )
2097 132 R Eth Port 1
Full Duplex
Enabled
Actual duplex mode
True = Full Duplex
False = Half Duplex.
- 134 R Eth Port 1
Autonegotiate
State
Active state of the Auto-Negotiation
behavior.
Value = State
0 = Link Inactive
1 = Auto Negotiation in Progress
2 = Auto Negotiation Failed (Default
used)
3 = Auto Negotiation of Duplex Failed
(speed ok)
4 = Auto Negotiation Success
5 = Auto Negotiation Disabled
6 = Port Disabled
2145 135 R Eth Port 1
Enabled
This parameter can disable the Ethernet
Port. Effectively disabling the port.
True = Enable Port
False = Disable Port
- 137 R Eth Port 2
Speed Actual
Actual Ethernet link speed. ( Mbs )
2209 139 R Eth Port 2
Full Duplex
Enabled
Actual duplex mode.
True = Full Duplex
False = Half Duplex
- 141 R Eth Port 2
Autonegotiate
State
Active state of the Auto-Negotiation
behavior.
Value = State
0 = Link Inactive
1 = Auto Negotiation in Progress
2 = Auto Negotiation Failed (Default
used)
3 = Auto Negotiation of Duplex Failed
(speed ok)
4 = Auto Negotiation Success
5 = Auto Negotiation Disabled
6 = Port Disabled
2257 142 R Eth Port 2
Enabled
This parameter Indicates whether an
Ethernet port is enabled.
True = Port Enabled
False = Port Disabled
- 143 R Method of IP
Allocation
The method used to allocate an IP
Address:
0 - DHCP
1 - Upper three octets from NV and
lower octet selected by the dip switch
setting.
2 - Full address taken from NV Memory.
3 - Restore (hardcoded 192.168.1.254).
Table 102. Register Definitions for S811+ Soft Starter (Cont.)
Start
Coil Register
Read/
Write Name Description (Units)
- 144 R Present
Ethernet IP
Address
The active IP address being used on the
network.
- 146 R Present
Ethernet
Subnet Mask
The active subnet mask IP address being
used on the network.
- 148 R Present
Ethernet
Default
Gateway
The active default gateway IP address
being used on the network.
- 150 R/W Stored
Ethernet IP
Address
The IP address used in the NV address
select configuration.
- 152 R/W Stored
Ethernet
Subnet Mask
The IP subnet mask used in the NV
address select configuration.
- 154 R/W Stored
Ethernet
Default
Gateway
The IP default gateway used in the NV
address select configuration.
- 156 R/W Ethernet MAC
Address
Unique MAC Address assigned to this
device.
- 159 R/W Modbus Com
Timeout
Communication timeout for Modbus. 0 =
Disable. ( milliseconds )
- 160 R/W Modbus TX
mode
Selects the Modbus Mode.
0 - RTU
1 - ASCII
- 161 R/W Modbus Baud
Rate
Selects the Modbus baud rate.
0 - 19.2kb
1 - 9.6kb
2 - 57.6kb
3 - 115.2kb
- 162 R/W Modbus
Address
Modbus address loaded at startup.
- 163 R/W Modbus Parity
and Stop Bits
Selects the Modbus UART parity and
Stop Bits.
0 - Even/One Stop Bit
1 - Odd/One Stop Bit
2 - None/Two Stop Bits
3 - Even/Two Stop Bits
4 - Odd/Two Stop Bits
5 - None/One Stop Bit
3201 201 R Intercom
Status
Present state of the Intercom Link.
Bit - Status
0 - Connected fully. No error messages.
1 - A message fault occurred.
2 - Devices are married. Target is identi-
fied and correct.
3 - A basic connection is established.
4033 253 R/W Motor Ctrl
Com Idle Act
Disable
When this value is TRUE the motor state
will be unchanged after a communication
idle event. A FALSE value will cause the
Motor Control Communication Idle Value
to be applied on a com idle event.
4049 254 R/W Motor Ctrl
Com Idle
Action Val
Action to execute when a communication
idle event occurs.
0 = Ignore (No Change)
1 = Stop
- 255 R/W EtherNet/IP
Comm Timeout
EtherNet/IP communication timeout
Range: 0–60,000 ms
Default: 3000 ms
- 256 R/W Encapsulation
Inactivity
Timeout
Number of seconds of inactivity before
TCP connection is closed