7.4 Register Definition for the S611 Soft Starter
Table 101. Register Definition for the S611 Soft Starter
Start
Coil Register
Read/
Write Name Description (Units)
1 1 R Field Inputs A Bitfield Representing the Input Points.
Bit = Description
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
- 2 R Control Voltage Adapter Source Voltage. ( mV )
- 3 R Ambient
Temperature
Device ambient temperature as mea-
sured from the PCB. ( ºC )
- 4 R/W Max Board
Temperature
The maximum board temperature experi-
enced since manufacturing. ( ºC )
65 5 R Dip Switch
Value
A bit field representing the present state
of the dip switches.
- 6 R Configuration
CRC
A CRC value calculated over the non-
volatile data present.
- 7 R/W Serial Number 32 bit Com Adapter Device Serial
Number.
- 9 R Firmware Rev Com Adapter Firmware Rev.
- 11 R/W Hardware Rev Com Adapter Hardware Rev.
1601 101 R/W Field Relay
Outputs
A Bitfield Representing the Output
Points.
Bit = Description
0 = Output 1
1 = Output 2
- 102 R/W Field Inputs
Debounce
Array of debounce values. A debounce
value exists for each input. The
debounce applies to both rising and fall-
ing edge. ( milliseconds )
- 110 R/W Modbus TCP
Com Timeout
Communication Timeout for Modbus
TCP. 0 = Disable. ( milliseconds )
1761 111 R/W Field Relay
Fault Action
When a communication fault occurs
the relays can execute two types of
behavior. The behavior is selected on a
per bit basis.
Bit = Description
0 = Relay 1
1 = Relay 2
Bit Value = Description
0 = Apply Fault Value
1 = No Change
1777 112 R/W Field Relay
Fault State
Communication fault value to be
applied. A bitfield where each bit
defines an output point.
Bit Value = Description
0 = Turn Relay Off
1 = Turn Relay On
1793 113 R/W Field Relay Idle
Action
When a communication idle state occurs
the relays can execute two types of
behavior. The behavior is selected on a
per bit basis.
Bit = Description
0 = Relay 1
1 = Relay 2
Bit Value = Description
0 = Apply Idle Value
1 = No Change
1809 114 R/W Field Relay Idle
State
Communication idle value to be applied.
A bitfield where each bit defines an
output point.
Bit Value = Description
0 = Turn Relay Off
1 = Turn Relay On
Table 101. Register Definition for the S611 Soft Starter (Cont.)
Start
Coil Register
Read/
Write Name Description (Units)
- 143 R Method of IP
Allocation
The Method Used to Allocate an IP
Address:
0 - DHCP
1 - Upper three octets from NV and
lower octet selected by the dip switch
setting.
2 - Full address taken from NV Memory.
3 - Restore (hardcoded 192.168.1.254).
- 144 R Present
Ethernet IP
Address
The active IP address being used on the
network.
- 146 R Present
Ethernet Subnet
Mask
The active subnet mask IP address being
used on the network.
- 148 R Present
Ethernet
Default
Gateway
The active default gateway IP address
being used on the network.
- 150 R/W Stored Ethernet
IP Address
The IP address used in the NV address
select configuration.
- 152 R/W Stored Ethernet
Subnet Mask
The IP subnet mask used in the NV
address select configuration.
- 154 R/W Stored Ethernet
Default
Gateway
The IP default gateway used in the NV
address select configuration.
- 156 R/W Ethernet MAC
Address
-
- 159 R/W Modbus Com
Timeout
Communication Timeout for Modbus.
0 = Disable. ( milliseconds )
- 160 R/W Modbus TX
mode
Selects the Modbus Mode.
0 - RTU
1 - ASCII
- 161 R/W Modbus Baud
Rate
Selects the Modbus Baud Rate.
0 - 19.2kb
1 - 9.6kb
2 - 57.6kb
3 - 115.2kb
- 162 R/W Modbus
Address
Modbus address loaded at startup.
- 163 R/W Modbus Parity
and Stop Bits
Selects the Modbus UART Parity and
Stop Bits.
0 - Even/One Stop Bit
1 - Odd/One Stop Bit
2 - None/Two Stop Bits
3 - Even/Two Stop Bits
4 - Odd/Two Stop Bits
5 - None/One Stop Bit
3201 201 R Intercom Status Present State of the Intercom Link.
Bit - Status
0 - Connected fully. No error messages.
1 - A message fault occurred.
2 - Devices are married. Target is identi-
fied and correct.
3 - A basic connection is established.
4001 251 R/W Motor Ctrl
Idle Loss Act
Disable
When this value is TRUE the motor state
will be unchanged after a communica-
tion idle event. A FALSE value will
cause the Motor Control Communication
Idle Value to be applied on a com idle
event.
4017 252 R/W Motor Ctrl Com
Idle Action Val
Action to execute when a communica-
tion loss event occurs.
0 = Ignore (No Change)
1 = Stop
4033 253 R/W Motor Ctrl
Com Loss Act
Disable
When this value is TRUE the motor state
will be unchanged after a communica-
tion loss event. A FALSE value will
cause the Motor Control Communication
Loss Value to be applied on a com loss.
4049 254 R/W Motor Ctrl Com
Loss Action Val
Action to execute when a communica-
tion loss event occurs.
0 = Ignore (No Change)
1 = Stop