C441 Ethernet module user manual
(C441R, C441T, C441U, C441V)
EATON www.eaton.com
Table 101. Register Definition for the S611 Soft Starter (Cont.)
Start
Coil Register
Read/
Write Name Description (Units)
- 255 R/W EtherNet/IP
Comm Timeout
EtherNet/IP communication timeout
Range: 0–60,000 ms
Default: 3000 ms
- 256 R/W Encapsulation
Inactivity
Timeout
Number of seconds of inactivity before
TCP connection is closed
- 300 R Motor Status Motor Control Status Bits:
Bit = Description
0 = Run
2 = In Bypass
5 = Fault
11 = Relay 1 State
12 = Relay 2 State
13 = Control From Network
14 = Permissive State
- 301 R Current Scale
Factor
Scale Factor for Current. Use this value
to scale the current values.
- 302 R Phase A RMS
Current
Scaled RMS Current of Phase A. (Amps)
- 303 R Phase B RMS
Current
Scaled RMS Current of Phase B. (Amps)
- 304 R Phase C RMS
Current
Scaled RMS Current of Phase C. (Amps)
- 305 R Average
Current
Average of the 3 Scaled RMS Currents.
( Amps )
- 306 R Vab RMS
Voltage
RMS line-to-line voltage measured
between phase A and B. ( Volts )
- 307 R Vbc RMS
Voltage
RMS line-to-line voltage measured
between phase B and C. ( Volts )
- 308 R Vca RMS
Voltage
RMS line-to-line voltage measured
between phase C and A. ( Volts )
- 309 R Average
Voltage
Average of the 3 Scaled RMS Voltages
( Volts )
- 310 R Total Kilowatts Scaled Total Kilowatts. Scale factor is
x10 ( kW )
- 311 R Apparent
Power Factor
Apparent Power Factor * 100
- 312 R Power Sign Indicates whether power is positive or
negative. In the case of a generator.
- 313 R Line Frequency Scaled Line Frequency. Scaling is x100.
( Hz )
- 314 R Overload
Thermal
Memory
Thermal Capacity
0% Cold Motor
100% Will Cause an Overload Trip ( % )
- 315 R Current
Unbalance
Percent Current Phase Imbalance. ( % )
- 316 R Voltage
Unbalance
Voltage Unbalance Percent. ( % )
- 317 R Residual
Ground Fault
Current
Scaled Residual Ground Fault Current.
Scaling = x100
- 318 R Phase A Pole
Temp
Power Pole Temperature. Scaled = x10
( ºC )
- 319 R Phase B Pole
Temp
Power Pole Temperature. Scaled = x10
( ºC )
- 320 R Phase C Pole
Temp
Power Pole Temperature. Scaled = x10
( ºC )
- 321 R Pole Temp Average Power Pole Temperature.
Scaled = x10 ( ºC )
- 322 R Number of
Starts
Total number of starts can be reset
through the command parameter.
- 323 R Total Run Time Run time in hours. Total run time can be
reset through the command parameter.
( Hours )
Table 101. Register Definition for the S611 Soft Starter (Cont.)
Start
Coil Register
Read/
Write Name Description (Units)
- 324 R Trip Reason Bit = Description
0 = Overload
1 = Jam
2 = Stall
3 = Current Imbalance
4 = Load Disconnect
5 = Phase Loss
6 = Mains Fault
7 = Phase Reversal
8 = Shorted SCR
9 = SCR Not Firing
10 = Pole Overtemp
11 = Bypass Dropout
12 = SCR Overcurrent
13 = Contactor Overcurrent
14 = Communication Fault
15 = Other Device Fault
- 325 R Fault Code Fault Code and Fault Code List. When
read as a single item it is the most
recent fault. When read as a list, faults
are listed in history order. Newest are
at the beginning, oldest are at the end
of the list.
If the device is in the Faulted state,
Fault Code indicates the fault that
caused the transition to Faulted state.
If not in the Faulted state, the Fault
Code indicates the fault that caused the
last transition to the Faulted state.
- 335 R Orion Firmware
Revision
-
- 336 R Orion Firmware
Build
-
- 337 R Orion UI
Firmware
Firmware Version for the User Interface.
- 338 R Unit ID Descriptive Product Identifier.
- 399 R/W Modbus
Change Tracker
Queue
-
- 400 R/W Motor Control Motor Control Bits:
Bit = Description
0 = Run
2 = Permissive
3 = Reset
- 401 R/W Start Input
Behavior
Selects the behavior for the start input.
When edge is selected, a start will only
be performed on the rising edge of the
start input. When level is selected, a
start will occur any time the input is
high.
0 = Edge
1 = Level
- 402 R/W Command
Register
1 = Clear Motor Run Hours
2 = Clear Motor Start Count
3 = Clear Fault Queue
255 = Force Overload Rest (TP = 0)
250 = Force Comm Fault (Unpublished)
- 403 R/W Configuration
Reset
1 = Soft Reset
2 = Factory Defaults
- 404 R/W Scaled
Overload FLA
Scaled Overload FLA. Scaling factor is
x10. ( Amps )
- 405 R/W Rated Voltage Rated Voltage of the Motor.
- 406 R/W Start Method Motor Start Method:
0 = Vramp
1 = Limit
2 = Pump
Note: If special function bit 0 is set,
then pump option is available and set
as the default, otherwise ramp start (0)
is default
- 407 R/W Start Time Motor Start Ramp Time. ( deciseconds )
- 408 R/W Initial Motor
Torque
Starting (Initial) Torque Percent.