27
User Manual MN04200002E
Effective January 2016
C441 Ethernet module user manual
(C441R, C441T, C441U, C441V)
EATON www.eaton.com
Class 41 (0x29): Control Supervisor Object
Instance Count: 1
Instance List: 1
Table 45. C440 Control Supervisor Instance Attributes
Attrib NV Access
Data
Type Name Description
10 V Get BOOL Fault Status A Fault has occurred. Faults are
latching and require a reset.
12 V Set/Get BOOL Fault Reset 0->1 Causes a reset.
17 V Set/Get BOOL Force Fault 0->1 = Force Fault
0 = No action
101 V Get WORD Device
Status
Device Bit Array
Bit 0: Tripped
Bit 1: Unused
Bit 2: Output #1
Bit 3: Output #2
Bit 4: Input #1
Bit 5: Input #2
Bit 6: Input #3
Bit 7: Input #4
Bit 8: Overload Power Lost
Bit 9: Comm Adapter Low Voltage
Bit 10: 1=Running, 0=Stopped or
Tripped
Bit 11-15: Reserved
102 V Get UINT Latched
Faults
Faults are cleared when the device is
either reset by the network or detects
current flowing
The fault bits are defined as follows:
Bit Feature
0 Overload Fault
1 Phase Imbalance
2 Phase Loss Fault
3 Ground Fault
4 Network Trip Command
5 NV Memory Failure
6-> Reserved
103 V Get USINT Motor Ctrl
State
Motor Control States:
0 = Stopped
1 = Running
2,3 = Tripped
4 = Resetting
105 NV Set/Get BOOL Motor Ctrl
Idle Loss Act
Disable
When this value is TRUE the motor
state will be unchanged after a
communication idle event. A FALSE
value will cause the Motor Control
Communication Idle Value to be
applied on a com idle event.
106 NV Set/Get BOOL Motor Ctrl
Com Idle
Action Val
Action to execute when a communi-
cation loss event occurs.
0 = Ignore (No Change)
1 = Stop
107 NV Set/Get BOOL Motor Ctrl
Com Loss
Act Disable
When this value is TRUE the motor
state will be unchanged after a
communication loss event. A FALSE
value will cause the Motor Control
Communication Loss Value to be
applied on a com loss.
108 NV Set/Get BOOL Motor Ctrl
Com Loss
Action Val
Action to execute when a communi-
cation loss event occurs.
0 = Ignore (No Change)
1 = Stop
Table 45. C440 Control Supervisor Instance Attributes (Cont.)
Attrib NV Access
Data
Type Name Description
130 V Get UINT Feature
States
The feature status bits are defined
as follows:
Bit Feature
01 Class Index (00 = Class 10;
01 = Class 15; 10 = Class 20; 11 =
Class 30)
2 Phase Loss/Imbalance Enabled
3 Ground Fault Enabled
4 Auto Reset Enabled
5 Remote Reset Active
6 Dip Switch Position 0
7 Dip Switch Position 1
8 Dip Switch Position 2
9 Dip Switch Position 3
10-15 Reserved
131 V Get INT Device
Temperature
The temperature as seen by the
microcontroller. Accuracy ~ 10%.
(°C)
132 V Get UINT Line
Frequency
The line frequency measured by the
device. The frequency is displayed in
deciHz. (Hertz)
133 NV Set/Get UINT EtherNet/IP
Comm
Timeout
Range: 0–60,000 ms
Default: 3000 ms

Related product manuals