Table 47. S611 Identity Object Instance Attributes (Cont.)
Attrib NV Access
Data
Type Name Description
5 V Get WORD Device
Status
This attribute represents the current
status of the entire devices. Its
value changes as the state of the
device changes.
Bit = Definition
0 = Owned. True indicates the
device has an owner.
2 = Configured. True indicates
the application of the device has
been configured to do something
different than out of box default.
Does not include communication
configuration.
4-7 = Extended Device Status.
8 = Minor Recoverable Fault. True
indicates the device detected
a problem with itself, which is
thought to be recoverable.
9 = Minor Unrecoverable Fault.
True indicates the device detected
a problem with itself, which is
thought to be unrecoverable.
10 = Major Recoverable Fault.
True indicates the device detected
a problem with itself causing a
“Major Recoverable Fault” state.
11 = Major Unrecoverable Fault.
True indicates the device detected
a problem with itself causing a
“Major Unrecoverable Fault” state.
6 NV Set/Get UDINT Serial
Number
32 bit Com Adapter Device Serial
Number.
7 V Get SHORT_
STRING
Product
Name
ASCII Product Name.
8 V Get USINT Device
State
Present State of the Device.
Value = Definition
0 = Nonexistent
1 = Device Self Testing
2 = Standby
3 = Operational
4 = Major Recoverable Fault
5 = Major Unrecoverable Fault
255 = Default for Get Attributes All.
176 NV Set/Get SHORT_
STRING
Assigned
Name
User Defined ASCII Name.
177 V Get UINT C441
DSP FW
Version
C441 DSP Firmware Version
178 V Get UINT UI
Firmware
Version
User Interface Firmware Version
179 NV Set/Get UINT C441
Unit ID
Unit ID
0x00BA (186) - C441BA
0x00BB (187) - C441BB
0x00CA (202) - C441CA
0x00CB (203) - C441CB
0x00DA (218) - C441DA
0x00DB (219) - C441DB
0x00EA (234) - C4410109(x)
0x00EB (235) - C4410590(x)
Class 4 (0x04): Assembly Object
Instance Count: 10
Instance List: 3, 60, 100, 105, 106, 107, 108, 121, 131, 133
Table 48. S611 Assembly Instance Attributes
Attrib NV Access
Data
Type Name Description
3 V Set/Get Array of
BYTE
Data Assembly Data. See sections
below for instance definition.
Table 49. S611 Assembly Instance List:
Type Instance Usage Name
Output 3 Poll Basic Softstarter
Input 60 Poll Basic Softstarter Input
Input 100 Poll Status and Current
Output 105 Poll Basic Overload w/Relay
Output 106 Poll Extended Motor Ctrl
Input 107 Poll Extended Overload w/ IO
Input 108 Poll Motor Ctrl Status w/IO
Input 121 Poll Status Measurement and Thermal
Input 131 Poll Status and Enhanced Measurement
Input 133 Poll Full S611 Monitoring
Assembly Instance Definitions:
Table 50. S611 Assembly Instance 3 (0x03): Basic Softstarter
Byte
Offset
Word
Offset
Size
(bytes) Name Description
0 0 1 Basic
Softstarter
Basic Softstart Assembly.
Bit 0 = Run 1
Bit 2 = Fault Reset
Total Assembly Size (bytes): 1
Table 51. S611 Assembly Instance 60 (0x3C): Basic Softstarter
Input
Byte
Offset
Word
Offset
Size
(bytes) Name Description
0 0 1 Basic
Softstarter
Input
Basic Softstart.
Bit 0 = Faulted
Bit 2 = Running1
Bit 7 = Bypass (at Reference)
Total Assembly Size (bytes): 1
Table 52. S611 Assembly Instance 100 (0x64): Status and Current
Assembly includes the status overview and motor current levels.
Word Size (bytes): 2
All data is little endian (low byte first).
Byte
Offset
Word
Offset
Size
(bytes) Name Description
0 0 2 Device Status Device Bit Array, Bit:
0: Fault
1: Bypass
2: Running1
3: S611 Run/Aux Relay (Relay 1)
4: S611 Fault Relay (Relay 2)
5: CtrlFromNet
6: Permissive
7: Reserved
8: Output #1
9: Output #2
10: Input #1
11: Input #2
12: Input #3
13: Input #4
14: DeviceNet Low Power
15: S611 Intercom Lost
2 1 2 Phase A RMS
Current
Scaled RMS current of phase A. (Amps)
4 2 2 Phase B RMS
Current
Scaled RMS current of phase B. (Amps)
6 3 2 Phase C RMS
Current
Scaled RMS current of phase C. (Amps)
Total Assembly Size (bytes): 8