Table 62. S611 Control Supervisor Instance Attributes (Cont.)
Attrib NV Access
Data
Type Name Description
153 NV Set/Get UINT Auxiliary Relay
Configuration
Auxiliary Relay Configuration
Behavior:
0 = Faulted
1 = Not Faulted
2 = Bypass
3 = Not In Bypass
4 = Motor Energized
5 = Motor Not Energized
154 NV Set/Get UINT User Interface
Display Config
User Interface Display
Configuration.
Value = Description
0 = Thermal Capacity
1 = Power Factor
2 = Line Frequency
3 = Current Unbal %
4 = Voltage Unbalance %
5 = Average pole temp
6 = Pole A Temp
7 = Pole B Temp
8 = Pole C Temp
155 NV Set/Get UINT UI Edit Lock Provides the ability to prevent
the user interface from making
configuration changes.
0 = Unlocked
1 = Locked
156 V Set/Get UINT Command
Register
1 = Clear Motor Run Hours
2 = Clear Motor Start Count
3 = Clear fault queue
255 = Force Overload Rest
(TP = 0)
250 = Force Comm Fault (unpub-
lished)
157 NV Set/Get UINT Communication
Loss Timeout
Communication Loss Timeout
Value (milliseconds)
158 NV Set/Get UINT EtherNet/IP
Comm Timeout
Range: 0–60,000 ms
Default: 3000 ms
Class 44 (0x2C): Overload Object
Instance Count: 1
Instance List: 1
Table 63. S611 Overload Object Instance Attributes
Attrib NV Access
Data
Type Name Description
4 NV Set/Get USINT Overload Class Overload Trip Class Setting.
6 V Get USINT Current
Unbalance
Percent Current Phase Imbalance.
(%)
7 V Get USINT Overload
Thermal
Memory
Thermal Capacity
0% Cold Motor
100% Will Cause an Overload
Trip (%)
101 V Get UINT Total Run Time Run Time in Hours. Total run time
can be reset through the command
parameter. (Hours)
102 V Get UINT Number of
Starts
Total number of starts can be reset
through the command parameter.
105 NV Set/Get UINT Scaled Overload
FLA
Scaled Overload FLA. Scaling fac-
tor is x10. (Amps)
106 V Get UINT Apparent Power
Factor
Apparent Power Factor * 100
107 V Get UINT Total Kilowatts Scaled Total Kilowatts. Scale fac-
tor is x10 (kW)
119 NV Set/Get UINT Current
Unbalance Trip
Delay
Trip Delay Applied to the
Unbalance Trip. (Seconds)
120 V Get UINT Current
Unbalance
Percent Current Phase Imbalance.
(%)
121 NV Set/Get UINT Jam Trip Delay Jam Trip Delay in Seconds. (sec-
onds)
122 NV Set/Get UINT Jam Trip Level Jam Trip Level Set in Percent of
FLA. (%)
123 NV Set/Get UINT Phase Loss Trip
Delay
Trip Delay Applied to the Phase
Loss Trip Sense. (seconds)
130 NV Set/Get UINT Reset Mode Method of Reset.
0 = Manual
1 = Auto
140 V Get UINT Average Current Average of the 3 Scaled RMS
Currents. (Amps)
141 V Get UINT Phase A RMS
Current
Scaled RMS Current of Phase A.
(Amps)
142 V Get UINT Phase B RMS
Current
Scaled RMS Current of Phase B.
(Amps)
143 V Get UINT Phase C RMS
Current
Scaled RMS Current of Phase C.
(Amps)
144 V Get UINT Residual
Ground Fault
Current
Scaled Residual Ground Fault
Current. Scaling = x100
152 V Get UINT Current Scale
Factor
Scale Factor for Current. Use this
value to scale the current values.
170 NV Set/Get UINT Load Disconnect
Trip Level
Load Disconnect Trip Level as a
Percent of Rated FLA. (%)
171 NV Set/Get UINT Load Disconnect
Trip Delay
Load Disconnect Trip Delay in
Seconds. (seconds)
172 NV Set/Get UINT Load Disconnect
Source
Load Disconnect Source:
0 = Under Power
1 = Under Current
173 NV Set/Get UINT Phase Loss Trip
Level
Trip Level for a Phase Imbalance
Trip. (%)
174 NV Set/Get UINT Stall Trip Level Stall Trip Level in Percent of FLA.
(%)
175 V Get INT Power Sign Indicates whether power is posi-
tive or negative. In the case of a
generator.
176 NV Set/Get UINT Residual GF
Start Delay
Length of time before the device
will begin to acknowledge the
ground fault current. (seconds)