EasyManua.ls Logo

Eaton C441R - Page 36

Eaton C441R
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
36
User Manual MN04200002E
Effective January 2016
C441 Ethernet module user manual
(C441R, C441T, C441U, C441V)
EATON www.eaton.com
Table 65. S811+ Identity Object Instance Attributes (Cont.)
Attrib NV Access
Data
Type Name Description
5 V Get WORD Device
Status
This attribute represents the current
status of the entire devices. Its
value changes as the state of the
device changes.
Bit = Definition
0 = Owned. True indicates the
device has an owner.
2 = Configured. True indicates
the application of the device has
been configured to do something
different than out of box default.
Does not include communication
configuration.
4-7 = Extended Device Status.
8 = Minor Recoverable Fault. True
indicates the device detected
a problem with itself, which is
thought to be recoverable.
9 = Minor Unrecoverable Fault.
True indicates the device detected
a problem with itself, which is
thought to be unrecoverable.
10 = Major Recoverable Fault.
True indicates the device detected
a problem with itself causing a
“Major Recoverable Fault” state.
11 = Major Unrecoverable Fault.
True indicates the device detected
a problem with itself causing a
“Major Unrecoverable Fault” state.
6 NV Set/Get UDINT Serial
Number
32 bit Com Adapter Device Serial
Number.
7 V Get SHORT_
STRING
Product
Name
ASCII Product Name.
8 V Get USINT Device
State
Present State of the Device.
Value = Definition
0 = Nonexistent
1 = Device Self Testing
2 = Standby
3 = Operational
4 = Major Recoverable Fault
5 = Major Unrecoverable Fault
255 = Default for Get Attributes All.
176 NV Set/Get SHORT_
STRING
Assigned
Name
User Defined ASCII Name.
177 V Get UINT C441
DSP FW
Version
C441 DSP Firmware Version
178 V Get UINT UI
Firmware
Version
User Interface Firmware Version
179 NV Set/Get UINT C441
Unit ID
Unit ID
0x00BA (186) - C441BA
0x00BB (187) - C441BB
0x00CA (202) - C441CA
0x00CB (203) - C441CB
0x00DA (218) - C441DA
0x00DB (219) - C441DB
0x00EA (234) - C4410109(x)
0x00EB (235) - C4410590(x)
Class 4 (0x04): Assembly Object
Instance Count: 14
Instance List: 5, 60, 61, 101, 102, 110, 111, 120, 121, 130, 131,
140, 141, 150
Attrib NV Access
Data
Type Name Description
3 V Set/Get Array of
BYTE
Data Assembly Data. See sections
below for instance definition.
Table 66. Assembly Instance List:
Type Instance Usage Name
Output 5 (0x05) Poll Extended Softstarter Output
Input 60 (0x3C) Poll Basic Softstarter Input
Input 61 (0x3D) Poll Extended Softstarter Input
Output 101 (0x65) Poll Extended Softstarter Output with Relay Outs
Input 102 (0x66) Poll Device Status
Input 110 (0x6E) Poll Status and Current(A)
Input 111 (0x6F) Poll Status and Current(0.1A)
Input 120 (0x78) Poll Status measurement and Thermal, Current in Amps
Input 121 (0x79) Poll Status measurement and Thermal. Current in 0.1A
Input 130 (0x82) Poll Status,Current,Voltage,Thermal, Current in Amps
Input 131 (0x83) Poll Status,Current,Voltage,Thermal, Current in 0.1A
Input 140 (0x8C) Poll Full S811 Monitoring, Current in Amps
Input 141 (0x8D) Poll Full S811 Monitoring, Current in 0.1A
Input 150 (0x96) Poll S811 Status
Assembly Instance Definitions:
All Assembly data is little endian (low byte first).
Table 67. Assembly Instance 5 (0x05): Extended Softstarter
Output
Byte
Offset
Word
Offset
Size
(bytes) Name Description
0 0 1 Extended
Softstarter
Extended softstart assembly.
Bit = Description
0 = Run 1
1 = Run 2 (Ramp2)
2 = Fault Reset
Total Assembly Size (bytes): 1

Related product manuals