39
User Manual MN04200002E
Effective January 2016
C441 Ethernet module user manual
(C441R, C441T, C441U, C441V)
EATON www.eaton.com
Table 77. Assembly Instance 131 (0x83):
Status,Current,Voltage,Thermal (0.1A)
Assembly includes the status overview, motor current levels scaled in 0.1A, Pole Voltages
& Thermal.
Word Size (bytes): 2
Byte
Offset
Word
Offset
Size
(bytes) Name Description
0 0 2 Device
Status
Device Status Bit Array
0 Running - RUN command active
1 Jogging - Jog command active
2 Permissive - Start allowed (must be 1
to start)
3 Ramp2 - Ramp2 settings active
4 Local Control (0 - network; 1 - local)
5 Faulted - S811+ fault present
6 Warning - S811+ warning present (self
clearing)
7 In bypass - S811+ Bypass closed
8 = Output 1
9 = Output 2
10 = Input 1
11 = Input 2
12 = Input 3
13 = Input 4
14 = Alarm No Trip Enabled
15 = S811+ Internal Comm Loss
2 1 6 3Ph RMS
Line Current
(deciamps)
Scaled RMS 3phase line current - This is the
actual current flowing to the motor in 0.1A.
8 4 1 % Thermal
Pile used
Thermal Pile Used Percentage - Trip at
100%
10 5 2 Average
current as
% FLA
Average of the 3 phase current as a
percentage of the Motor Nameplate
flasetting
12 6 6 3Ph RMS
Mains
Voltage
3 Phase RMS Mains voltage reading (in
volts)
Total Assembly Size (bytes): 18
Table 76. Assembly Instance 130 (0x82):
Status,Current,Voltage,Thermal (A)
Assembly includes the status overview, motor current levels scaled in Amps, Pole
Voltages & Thermal.
Word Size (bytes): 2
Byte
Offset
Word
Offset
Size
(bytes) Name Description
0 0 2 Device
Status
Device Status Bit Array
0 Running - RUN command active
1 Jogging - Jog command active
2 Permissive - Start allowed (must be 1
to start)
3 Ramp2 - Ramp2 settings active
4 Local Control (0 - network; 1 - local)
5 Faulted - S811+ fault present
6 Warning - S811+ warning present (self
clearing)
7 In bypass - S811+ Bypass closed
8 = Output 1
9 = Output 2
10 = Input 1
11 = Input 2
12 = Input 3
13 = Input 4
14 = Alarm No Trip Enabled
15 = S811+ Internal Comm Loss
2 1 6 3Ph RMS
Line Current
(amps)
Scaled RMS 3phase line current - This is
the actual current flowing to the motor in
1.0A.
8 4 1 % Thermal
Pile used
Thermal Pile Used Percentage - Trip at
100%
10 5 2 Average
current as
% FLA
Average of the 3 phase current as a per-
centage of the Motor Nameplate fla setting
12 6 6 3Ph RMS
Mains
Voltage
3 Phase RMS Mains voltage reading (in
volts)
Total Assembly Size (bytes): 18