47
User Manual MN04200002E
Effective January 2016
C441 Ethernet module user manual
(C441R, C441T, C441U, C441V)
EATON www.eaton.com
Table 87. Class 140 (0x8C): Device Status Object (Cont.)
Attrib NV Access
Data
Type Name Description
8
(0x08)
V Get UINT Bit field
(warn-
ings)
S811+ Motor Control Warning Bit Field
Bit Warning
0 Phaseloss
1 Phase Imbalance
2 Thermal Pile
3 Overcurrent
4 Breaker Fault
5 GND Fault
6 Motor Stall
7 Motor Jam
8 OverTemp
9 UnderLoad
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 Other
9
(0x09)
V Get UINT Most
recent
fault
S811+ fault Queue
Queue will hold up to the last 10 faults -
Fault codes are not repeated in queue
10
(0x0A)
V Get UINT next
most
recent
fault
S811+ fault Queue
Queue will hold up to the last 10 faults -
Fault codes are not repeated in queue
11
(0x0B)
V Get UINT next
most
recent
fault
S811+ fault Queue
Queue will hold up to the last 10 faults -
Fault codes are not repeated in queue
12
(0x0C)
V Get UINT next
most
recent
fault
S811+ fault Queue
Queue will hold up to the last 10 faults -
Fault codes are not repeated in queue
13
(0x0D)
V Get UINT next
most
recent
fault
S811+ fault Queue
Queue will hold up to the last 10 faults -
Fault codes are not repeated in queue
14
(0x0E)
V Get UINT next
most
recent
fault
S811+ fault Queue
Queue will hold up to the last 10 faults -
Fault codes are not repeated in queue
15
(0x0F)
V Get UINT next
most
recent
fault
S811+ fault Queue
Queue will hold up to the last 10 faults -
Fault codes are not repeated in queue
16
(0x10)
V Get UINT next
most
recent
fault
S811+ fault Queue
Queue will hold up to the last 10 faults -
Fault codes are not repeated in queue
17
(0x11)
V Get UINT next
most
recent
fault
S811+ fault Queue
Queue will hold up to the last 10 faults -
Fault codes are not repeated in queue
18
(0x12)
V Get UINT Oldest
fault
S811+ fault Queue
Queue will hold up to the last 10 faults -
Fault codes are not repeated in queue
19
(0x13)
V Set/Get BOOL Clear
Fault
Queue
Set this parameter to TRUE to clear the
fault queue.
Table 88. Class 147 (0x93): Voltage Monitor Object
Instance Count: 1
Instance List: 1
Attrib NV Access
Data
Type Name Description
1
(0x01)
V Get UINT 3Ph RMS
Mains
Voltage
3 Phase RMS Mains voltage reading
(in volts)
(L1-L2)
2
(0x02)
V Get UINT 3Ph RMS
Mains
Voltage
3 Phase RMS Mains voltage reading
(in volts)
(L2-L3)
3
(0x03)
V Get UINT 3Ph RMS
Mains
Voltage
3 Phase RMS Mains voltage reading
(in volts)
(L3-L1)
4
(0x04)
V Get UINT Line
Frequency
Frequency reading of incoming mains
voltage (in 0.01Hz)
5
(0x05)
V Get USINT Incoming
Phase
Sequence
Phase sequence of incoming mains
voltage
0 - ABC
1 - ACB
6
(0x06)
V Get UINT DC Control
Voltage
DC Control Voltage reading in 0.001V
7
(0x07)
NV Set/Get UINT Motor Rated
Volts
Rated voltage of the motor
8
(0x08)
NV Set/Get USINT Under
Voltage Trip
Enable
Under voltage trip enable
0x00 - disable
0x01 - fault enable
0x02 - warning enable
9
(0x09)
NV Set/Get USINT Under
Voltage Trip
Threshold
Under voltage trip threshold (in per-
cent of rated motor voltage)
10
(0x0A)
NV Set/Get UINT Under
Voltage Trip
Duration
Amount of time an under voltage
condition must exist before a trip; 0.0 -
60.0 (in 0.1secs)
11
(0x0B)
NV Set/Get USINT Over Voltage
Trip Enable
Over voltage trip enable
0x00 - disable
0x01 - fault enable
0x02 - warning enable
12
(0x0C)
NV Set/Get USINT Over
Voltage Trip
Threshold
Over voltage trip threshold (in percent
of rated motor voltage)
13
(0x0D)
NV Set/Get UINT Over Voltage
Trip Duration
Amount of time an over voltage condi-
tion must exist before a trip; 0.0 - 60.0
(in 0.1secs)
14
(0x0E)
NV Set/Get USINT Voltage
Imbalance
Trip Level
Voltage imbalance trip threshold
15
(0x0F)
NV Set/Get UINT Voltage
Imbalance
Trip Duration
Amount of time a voltage imbalance
condition must exist before a trip; 0.0 -
60.0 (in 0.1secs)
16
(0x10)
NV Set/Get UINT Incoming
Line
Frequency
Rating
Expected frequency of incoming mains
voltage
17
(0x11)
NV Set/Get USINT Line
Frequency
Trip
Line frequency deviation trip enable
0x00 - disable
0x01 - fault enable
0x02 - warning enable
18
(0x12)
NV Set/Get USINT Frequency
Deviation
Trip
Threshold
Line frequency deviation trip threshold
(in percent of rated line frequency)
19
(0x13)
NV Set/Get UINT Frequency
Trip Duration
Amount of time a frequency deviation
condition must exist before a trip; 0.0 -
60.0 (in 0.1secs)
20
(0x14)
NV Set/Get USINT Phase
Reversal Trip
Enable
Phase reversal trip enable
0x00 - disable
0x01 - fault enable
0x02 - warning enable