52
User Manual MN04200002E
Effective January 2016
C441 Ethernet module user manual
(C441R, C441T, C441U, C441V)
EATON www.eaton.com
Table 99. Registers Available with C441 Motor Insight (Cont.)
Start
Coil Register
Read/
Write Name Description (Units)
- 327 R Remaining
Underload
Trip Restart
Delay
Load Fault - Time to Restart ( sec )
- 328 R/W Run Time
Hours
Motor Run Time in hours (resettable) ( hr )
- 329 R Start Count Start Count (Resettable)
- 330 R Trip Reason 0x0001 - Restart Attempts Exceeded
0x0002 - Relay Turned Off (Network/UI)
0x0004 - Contactor Failure
0x0008 - Under Current Trip
0x0010 - Overload Trip
0x0020 - GND Fault Trip
0x0040 - Current Unbalance Trip
0x0080 - Current Single Phase
0x0100 - Reserved (0)
0x0200 - High Power Trip
0x0400 - Over Voltage Trip
0x0800 - Under Voltage Trip
0x1000 - Voltage Unbalance Trip
0x2000 - Over Current Trip
0x4000 - Low Power Trip
0x8000 - Phase Reversal Trip
- 331 R Overload
Status
Overload Status
- 0x0001: Overload Trip
- 0x0002: Ground Fault Trip
- 0x0004: High Power Trip
- 0x0080: Relay Closed
- 332 R Error Code Warning/Alarm Indications
0x0001 (1) - Low Voltage Warning
0x0002 (2) - High Voltage Warning
0x0004 (4) - Voltage Unbalance Warning
0x0008 (8) - Low Power Warning
0x0010 (16) - Reverse Phase Warning
0x0020 (32) - Current Unbalance Warning
0x0040 (64) - Voltage Single Phase
Warning
0x0080 (128) - Current Single Phase
Warning
0x0100 (256) - GND Fault Warning
- 333 R C441 DSP
FW Version
C441 DSP Firmware Version
- 334 R UI Firmware
Version
User Interface Firmware Version
- 335 R/W C441 Unit ID Unit ID
0x00BA (186) - C441BA
0x00BB (187) - C441BB
0x00CA (202) - C441CA
0x00CB (203) - C441CB
0x00DA (218) - C441DA
0x00DB (219) - C441DB
0x00EA (234) - C4410109(x)
0x00EB (235) - C4410590(x)
5361 336 R Aux Relay
Trip Reason
0x0002 - Relay Turned Off (Network/UI)
0x0004 - Contactor Failure
0x0008 - Under Current Trip
0x0010 - Overload Trip
0x0020 - GND Fault Trip
0x0040 - Current Unbalance Trip
0x0080 - Current Single Phase
0x0100 - Mains Freq Fault
0x0200 - High Power Trip
0x0400 - Over Voltage Trip
0x0800 - Under Voltage Trip
0x1000 - Voltage Unbalance Trip
0x2000 - Over Current Trip
0x4000 - Low Power Trip
0x8000 - Phase Reversal Trip
Table 99. Registers Available with C441 Motor Insight (Cont.)
Start
Coil Register
Read/
Write Name Description (Units)
- 400 R/W Command
register
0x0066 - Clear Motor Run Hours
0x0077 - Clear Fault Queue 1
0x0078 - Clear Fault Queue
0x0088 - Network watchdog enable
0x0099 - Network watchdog disable
0x00AA - Reset Relay
0x00BB - Clear Motor Start Count
0x00CC - Force Ground Fault
0x00DD - Fault Relay OFF
0x00EE - Reset Auxiliary Relay (120 Vac
Control Power models only)
- 401 R/W Motor
Control
-
- 402 R/W Configuration
Reset
1 = Soft Reset (equivalent to a power
cycle)
2 = Factory Reset
- 403 R/W CT Multiplier For 90 Amp Units: 1-4, number of conduc-
tors through CT.
For 9 Amp Units: 1-2, number of conduc-
tors through CT;
For 9 Amp Units, CT multipliers: 3 (150:5),
4 (300:5), 5 (600:5)
- 404 R/W Ground Fault
Pick-up Level
Ground Fault Pick-up Level ( x0.01A )
- 405 R/W Under
Current Pick-
up Level
Under Current Pick-up Level ( % )
- 406 R/W Low Power
Pick-up Level
Low Power Pick-up Level ( x0.01kW )
- 407 R/W Overload FLA Motor Full Load Current ( x0.01A )
- 408 R/W Current
Unbalance
Pick-up Level
Current Unbalance Pick-up Level ( % )
- 409 R/W Overload Trip
Class
Overload Trip Class
- 410 R/W Under
Voltage Pick-
up Level
Under Voltage Pick-up Level ( V )
- 411 R/W Over Voltage
Pick-up Level
Over Voltage Pick-up Level ( V )
- 412 R/W Voltage
Unbalance
Pick-up Level
Voltage Unbalance Pick-up Level ( % )
- 413 R/W Jam Pick-up
Level
Jam Pick-up Level ( % )
- 414 R/W High KW Trip
limit
High Power Pick-up Level ( x0.01kW )
- 415 R/W Phase Order Phase Order
- 0 (Trip Disabled)
- 1 ACB
- 2 ABC
- 416 R/W Supply Fault
Hold-off Time
Restart Delay ( sec )
- 417 R/W Motor Fault
Hold-off Time
Motor Fault Reset Delay ( min )
- 418 R/W Load Fault
Hold-off Time
Load Fault Reset Delay ( min )
- 419 R/W Load Fault
Number of
Restarts
Load Fault Number of Reset Attempts
0: Manual
1-4
5: Automatic
- 420 R/W Motor Fault
Number of
Restarts
Motor Fault Number of Attempts:
0: Manual
1-4
5: Automatic
- 421 R/W Ground Fault
Trip Delay
Ground Fault Pickup Delay ( sec )
- 422 R/W Under
Current Trip
Delay
Under Current Trip Delay ( sec )
- 423 R/W Low Power
Trip Delay
Low Power Trip Delay ( sec )
- 424 R/W Jam Trip
Delay
Jam Trip Delay ( sec )