64
User Manual MN04200002E
Effective January 2016
C441 Ethernet module user manual
(C441R, C441T, C441U, C441V)
EATON www.eaton.com
Table 102. Register Definitions for S811+ Soft Starter (Cont.)
Start
Coil Register
Read/
Write Name Description (Units)
- 659 R/W Under Voltage
Trip Enable
Under voltage trip enable
0x00 - disable
0x01 - fault enable
0x02 - warning enable
- 660 R/W Under Voltage
Trip Threshold
Under voltage trip threshold (in percent
of rated motor voltage)
- 661 R/W Under Voltage
Trip Duration
Amount of time an under voltage condi-
tion must exist before a trip; 0.0 - 60.0
(in 0.1secs)
- 662 R/W Over Voltage
Trip Enable
Over voltage trip enable
0x00 - disable
0x01 - fault enable
0x02 - warning enable
- 663 R/W Over Voltage
Trip Threshold
Over voltage trip threshold (in percent
of rated motor voltage)
- 664 R/W Over Voltage
Trip Duration
Amount of time an over voltage condi-
tion must exist before a trip; 0.0 - 60.0
(in 0.1secs)
- 665 R/W Line Frequency
Trip
Line frequency deviation trip enable
0x00 - disable
0x01 - fault enable
0x02 - warning enable
- 666 R/W Frequency
Deviation Trip
Threshold
Line frequency deviation trip threshold
(in percent of rated line frequency)
- 667 R/W Frequency Trip
Duration
Amount of time a frequency deviation
condition must exist before a trip; 0.0 -
60.0 (in 0.1secs)
- 668 R/W Ave Power
Trip Enable
Average power trip enable
0x00 - disable
0x01 - fault enable
0x02 - warning enable
- 669 R/W Ave Power
Low Trip
Threshold
Low power trip threshold (in percent of
rated W)
rated W = sqrt(3)*0.8PF*motor fla*rated
motor voltage
- 670 R/W Ave Power
High Trip
Threshold
High power trip threshold (in percent of
rated W)
rated W = sqrt(3)*0.8PF*motor fla*rated
motor voltage
- 671 R/W Ave Power
Trip Duration
Amount of time a low or high power
condition must exist before a trip; 0.0 -
60.0 (in 0.1secs)
- 672 R/W Analog Input
Trip Enable
Analog input trip enable
0x00 - disable
0x01 - fault enable
0x02 - warning enable
- 673 R/W Analog Input
Trip Low
Threshold
Low analog input trip threshold (in per-
cent of selected analog range)
- 674 R/W Analog Input
Trip High
Threshold
High analog input trip threshold (in per-
cent of selected analog range)
- 675 R/W Analog Input
Trip Duration
Amount of time a low or high analog
input condition must exist before a trip;
0.0 - 60.0 (in 0.1secs)
- 676 R/W Temperature
Sensor Trip
Enable
Temperature sensor trip enable
0x00 - disable
0x01 - fault enable
0x02 - warning enable
- 677 R/W SCR Not Firing
Trip Enable
SCR not firing trip enable
0x00 - disable
0x01 - fault enable
0x02 - warning enable
- 678 R/W SCR Shorted
Trip Enable
Shorted SCR trip enable
0x00 - disable
0x01 - fault enable
0x02 - warning enable
Table 102. Register Definitions for S811+ Soft Starter (Cont.)
Start
Coil Register
Read/
Write Name Description (Units)
10849 679 R/W Alarm - No
Trip Enabled
Alarm no trip enable allows the S811+
to continue to run through any motor
faults. Fault will be issued but will not
stop the starter. Faults meant to protect
the softstarter will continue to trip the
starter
10865 680 R/W Start Delay
Active
Warning
Enable
Enables warning when start delay tim-
ers are used. Warning is issued while
start command is pending
- 681 R/W Start Delay
After Power
up
Time delay after power up before a start
command can be issued
- 682 R/W Start Delay Time delay after a start command is
issued before the S811+ will attempt
start
- 683 R/W Start Delay
After Run
Change
User settable time delay between suc-
cessive start profiles. Delay becomes
active when start profile(ramp vs ramp2)
changes between starts
- 684 R/W Motor Comm
Loss Action
Motor comloss action
0x00 - auto stop
0x01 - auto run1
0x02 - unavailable
0x03 - hold last state
0x04 - unavailable
0x05 - unavailable
0x06 - unavailable
0x07 - all stop fault (will trip S811+ and
issue all stop fault)
- 685 R/W Transient
Motor Control
Timeout
Motor control timeout for transient UI
devices
- 686 R/W Motor Control
Command
Timeout
Motor control timeout - communication
idle time which will cause a Motor
Control Device Missing fault
10977 687 R/W Network two
wire control
enable
Network two wire control parameter
enable
0 - 3wire control (Modbus reg #500
active)
1 - 2wire control (Modbus reg #501
active)
- 688 R/W GND Fault
Enable
GND fault trip enable
0x00 - disable
0x01 - fault enable
0x02 - warning enable
- 689 R/W GND Fault
Inhibit From
Start Delay
Parameter will mask the GND fault trip
from the end of start ramp; 0.0 - 20.0
in 0.1secs;
Example: ramp time = 20, GND delay
= 5, GND fault will be masked for 25
seconds after start command
- 690 R Firmware
Version List
Firmware version - AVR, DSP
- 692 R Hardware
Version
Hardware version
- 800 R/W Modbus
Device Reset
Register
Register performs reset services on
S811+ over modbus
0x00 - no reset
0x01 - soft reset (power cycle reset)
0x02 - factory reset (reset device back
to defaults)
0x03 - app parameter reset
0x04 - reserved
0x05 - reserved
0x06 - flush fault queue/list
- 900 R/W Modbus User
Application
Name
User defined ASCII name.