33-855-4
RMS 810 &
910 CELL
HARNESS
STYLE
NO. 6502C71G03
6503C57G03
CUSTOMER
CONNECTIONS
CUSTOMER
CONNECTIONS
AC120
ATRCOM
CUSTOMEB
CONNECTIONS
DG
LD
\lF
SC
HL
ACCOM
CELL
INTERFACE
PLUG
(RECEIVES
EXTERNAL
HARNESS)
Terminal
Block
Point
& Marking
DescriPtion
TBl-1
DG
Zone
lnterlock
Digital Ground
TBl-2
Gour
Zone
lnterlock Ground
Output
TBl-3
GtN
Zone
lnterlock
Ground lnput
TB1-4 5691
Zone lnterlock
Short
Delay Output
TB1-5 StN
Zone lnterlock
Short
Delay lnput
TB1-6
ACCOI\i]
ATR 120
Vac lnput Comm
fB2-1
AC
12O ATR
120
Vac lnput Power
TB2-2 ATRCOI\4
ATR Alarm
Contact Common-
TB2-3
LD
ATF Long
Delay
TriP Alarm.
f B2-4
GF
ATR Ground
Fault Trip Alarm.
TB2-5
SC
ATR Short
Circuit
Alarm.
T82-6
HL
ATR High
Load Alarm.
Terminal
Block
Point &
Marking
DescriPtion
TB3- 1 CC1
PowerNet
Contact
Output
to Breaker
Remote Close Contact*
rB3-2 CC2 PowerNet
Contact
Output
to Breaker
Remote
Close Contact*
TB3-3
COMI\,ll
PowerNet
Twisted
Pair Connection
TB3-4 COMI\,2
PowerNet
Twisted
Pair Connection
TB3-5
Free
Terminal
for Twisted
Pair Shield,
etc.
T83-6
Free Terminal
for
Twisted
Pair Shield, etc.
cc1
cc2
COMMl
cot\4M2
NOTICE:
.1.
Zone
lnterlock
Jumpers slX-s6y1
and
Glx-G6g1
must be installed
on TB1 or
Breaker
will trip instantaneously
on Short
Time
and Ground
Fault
Delay
functions. Remove
jumpers
ONLY
if Zone Interlocking
is required.
2.
All wiring terminators
shown are
furnished complete
with Fetrofit
Kit Wiring
Harness,
except
those
indicated
as
customer
connections.
.ATR
contacts
are
rated at
1 ampere
at 120 VAC
o|I ampere
at
28 VDC.
HL
COMM1
Fig.
12-14
Digitrip
RMS 810
& 910
Cell Harness
E:T.il
Effective 9 /01