Page 8 Effective June 2007
RS-485 PONI
66A2070 Rev. B
1's Complement of
Slave Action Byte1
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Slave Action Byte0
Slave Action Byte1
1's Complement of Slave Action Byte2
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Slave Action Byte2
1's Complement of Slave Action Byte0
Register 425089 (6200
16
)
Register 425091 (6202
16
)
Figure 13: Control to INCOM Product Data Format
Shipping List
• RS-485 PONI 66D2042 (x)
• Instruction Leaet 66A2070H02 (x)
• 5-pin Phoenix connector 9472A35H5 (x)
• Mounting screws 7000BU25R (x2)
Safety and Compliance Standards
EMC/Safety Standards:
• UL 3;CSA 00.
• CE Mark
• FCC Part 5, Class A
• EN 6000-6-2; 999
• EN 55011; 1998
EMC Susceptibility Standards:
• EN 6000-4-2; 995 Electro Static Discharge
• EN 6000-4-3; 998 Radiated RF Immunity
• EN 6000-4-4; 995 EFT and Burst
• EN 6000-4-5; 995 Voltage Surge
• EN 6000-4-6; 996 Conducted RF Immunity
• EN 6000-4-8; 994 Power Frequency Magnetic Field
• ANSI C37.90.2; 995 Radiated RF Immunity
• ANSI C37.90.; 989 Surge Withstand Capability
EMC Emissions Standards:
• FCC Part 5 Class A (0 meters)
• Radiated and Conducted Emissions
• EN 55011; 1998
• Radiated and Conducted Emissions
System Ratings
Operating Temperature –20°C to 60°C
Storage Temperature –20°C to 70°C
Altitude 3,048 m (10,000 ft.)
Operating Humidity 5% to 90% max. non-condensing
Environment Indoor use only
Transient Overvoltage Category
Pollution Degree 2
Equipment Class
3
Power Requirements 24V; 50 ma*
*The RS-458 PONI is powered by a limited source isolated
from the mains by double insulation. This source must be an
“SELV” voltage supply.
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Byte1 of Mantissa
Byte0 of Mantissa
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Byte3 of Mantissa
Byte2 of Mantissa
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Byte5 of Mantissa
Byte4 of Mantissa
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Engineering Units
Mantissa Multiplier
Energy Register 0
Energy Register 1
Energy Register 2
Energy Register 3
Energy = 2
Mantissa Multiplier
* Mantissa * 10
Engineering Units
Figure 14: Energy Register Data Format
Maintenance and Care
The RS-485 PONI is designed to be self-contained and
maintenance-free. The printed circuit board is calibrated and
coated at the factory.
The RS-485 PONI is intended for servicing by factory-trained
personnel only.
Never clean the RS-485 PONI while it is powered on. Clean
the RS-485 PONI using a clean, dry cloth and ensure that
the power is disconnected. Do not use water or solvents of
any kind.