MECHANICAL
Cutout Dimensions: 3.62 W x 1.77 H (92mm x 45mm) DIN standard
Outline Dimensions: 4.04 W x 2.19 H x 3.87 D (103mm x 56mm x 98mm)
3.60 (92mm) maximum depth in panel
Enclosure: Plastic with polyester front label
Connectors: Up to five de-pluggable terminal blocks
INPUT POWER
AC Powered Models (57701-4XX)
Input Power: 85-265 VAC, 47-63 Hz, 20 VA
External Fuse: 0.2A, 250 VAC, Time Delay (T200mA, 250V)
Isolation Dielectric Strength: 2300 VAC
DC Powered Models (57700-4XX)
Input Power: 9-30 VDC, 12 VA
External Fuse: 2.0A, 50 VDC, Time Delay (T2A, 50V)
Reverse Voltage Protection: Yes
Isolation Dielectric Strength: 2300 VAC to signal inputs and relays, 500 VAC
to RS485 and analog outputs
HUMAN INTERFACE
Display: +/- 4 full digits
Type: .56 high, seven segment, red LED
Update Time: 0.4 seconds
Alarm: Flashing display
Indicator: One red LED program/calibration indicator
with max./min. capture and hold
DATA RETENTION
Memory Type: EEPROM, no batteries required
Duration: 100 years
SIGNAL INPUT
DC Voltage Models (5770X-40X)
Range: +/- 199.9 mVDC, +/- 1.999 VDC, +/- 19.99 VDC, +/- 199.9 VDC,
DIP Switch Selectable
Impedance: 1 M W (ohms)
Overrange: 750 VDC/530 VAC except 220 VDC/AC on 199.9 mV range
Accuracy: +/- 0.1% of reading, +/- 0.03% FS, +/- 0.5 digit, and +/- 80 PPM/°C