20
Threshholds: High 3.5 to 28 VDC, low 0 to 1.9 VDC
Response: 25 msec max. (5 V signal)
ACCESSORY POWER OUTPUT
Voltage: 12 VDC +10%/-13%
Current: 75 mA max.
Protection: Short circuit protected
OPTIONAL OUTPUTS
Relay Board
Number of relays: 2
Contact type: 1 set form C per relay
Contact rating: 5A, 250 VAC or 30 VDC
Isolation dielectric strength: 2300 VAC
Analog Retransmission
Output signals: 4-20 mA (<750 W) and 0-10 V (>2500 W)
Accuracy: 0.13% full scale and 100 PPM /°C (and 0.07%
full scale change over 4-20 mA load ranges
Isolation dielectric strength: 2300 VAC to signal inputs, relays, and AC power
inputs, 500 VAC to RS 485 and DC power inputs
RS 485 Serial Communications
Baud Rate: 1200, 2400, 4800, 9600, or 19,200, programmable
Parity: Even, odd, or no parity
Address Range: 00 to 99 decimal
Protocol: Opto 22
®
compatible
Isolation Dielectric Strength: 2300 VAC to signal inputs, relays, and AC power
inputs, 500 VAC to analog outputs and DC
power inputs
ENVIRONMENTAL
Operating Environment: Indoor use to 2000 meters
Temperature: Operating: 0 to 50°C
Storage: -20 to 70°C
Humidity: 0 to 85% RH, non-condensing
Vibration: 2.5 gs, 30 to 200 Hz
Shock: 30 gs, 11 msec half sinewave
EMC: Immunity to EN 50082-2 (Heavy Industrial)
Emissions to EN 50081-2 (Heavy Industrial)
Front Panel: NEMA 4X when mounted with gasket provided
Agency Approval: UL, cUL listed, CE marked
CE EMC immunity and emissions requirements were met using
shielded wiring on the RS-485, analog output and pulse input/
power lines. The shields were connected to earth ground at the
Eclipse end of the shields.
Pollution Degree 2 Overvoltage category II
SPECIFICATIONS cont.