Output Personalization
ON/OFF Personalization
Battery Personalization
4.4 Personalization Using External Software
w Insert the Solution-Pac CD-ROM in the drive.
w On the first navigation screen, select “Point to Point solution” and follow the instructions on how to install the
Personal Solution-Pac software.
w Then select “Settings”, “Advanced settings” and “UPS settings”.
Note that the Linux/Unix/MacOS versions of the Personal Solution-Pac software do not offer this possibility.
(1). These Parameters may be modified only when the UPS is OFF.
(2). Bypass is disabled when frequency converter is enabled.
Function Factory Setting Options
Comments
Output voltage
(1)
120 Volts AC 100/104/110/120/127 Volts AC
Frequency converter
(1)
Disabled Enabled
(2)
The connected devices are never
transferred to the bypass.
Output frequency
(1)
Automatic selection 50 or 60 Hz
User selectable only if the
frequency-converter function is
enabled.
Transfer to the bypass
AC input
(1)
Bypass AC power must be
within tolances
Bypass AC power may be
outside tolerances
Overload level
(1)
102% 50 / 70% Alarm if threshold is overrun.
Function Factory Setting Options Comments
Battery test Weekly test
No test / daily test / monthly
test
Selection of the
backup time
Automatic detection of
number of battery modules
0 to 200 Ah
UPS restarts automatically when
Normal AC source is restored.
Battery protection
against excessive
discharges
Enabled Disabled
When function disabled, EATON
warranty no longer applies.
Function Factory Setting Options Comments
Start on battery power Enabled Disabled
Automatic restart Enabled Disabled
The UPS restarts automatically
when AC power returns.
Energy savings Disabled Enabled
When function enabled, battery
shuts down when power drops
to <5%.
Detection of phase/
neutral inversion
(SWF)
Enabled Disabled
When function enabled, the UPS
remains OFF if the system detects
phase/neutral inversion.
86-86710-00EN A02 - Page 22
4. Access to Maintenance and Personalization Data