5. POWER DERATING TABLE WITH EX RT 11
Input Voltage / Ambient Temperature 0 °C – 25 °C 25 °C – 35 °C 35 °C – 45 °C
220 – 280 Volts AC 100 % 100 % 100 %
200 – 220 Volts AC 100 % 95 % 90 %
180 - 200 Volts AC 90 % 85 % 80 %
160 – 180 Volts AC 80 % 75 % 70 %
6. DIMENSIONS & WEIGHT
Dimensions (H x W x D) (3U rack) 131 x 444 x 635 mm
Weight 12 kg
7. INSTALLATION
Installation in rack, we recommend placing the low frequency filter under the UPS.
For installation, please refer to the UPS installation and user manual.
8. LOW FREQUENCY FILTER CONNECTION
View of the low frequency filter module terminals :