34007724EN/AD - Page 25
BY
PASS
NORMAL
_
+
N
L
BATTERY
AC INPUT
2. Installation
Connection of CLA module
AC Input
To battery
Connect the battery cable z
28
(provided with the CLA module) between the power module and the CLA
module.
Connect the cable z
29
(provided with the CLA module) between the power module and the CLA module.
Connect the battery: z
- cable cross-section (not provided): 10 mm², solid or stranded wire (maximum 13 mm² or AWG 6).
Use a circuit-breaker (curve B, 50 A) for cable protection. z
Connect the input cable of the z CLA module to the AC input:
- AC input cable cross-section (not provided) : 2,5 mm².
Use a circuit-breaker (curve C, 10 A) for cable protection. z