Motion Sensors - Ceiling/Wall/Corner Mount
www.eaton.com/lightingsystems
Motion Sensors - Ceiling/Wall/Corner Mount
The Room Controller QuicKits use OAC (C1, C2, C3) or OAWC (W1, W2, W3) model sensors to allow for occupancy control.
Specifications
Voltage 10-30 VDC (24 VDC supplied from
Room Controller)
Electrical Class 2, LPS
Connections Wire leads connect to a provided
OCC-RJ45 Input/Output Device. The
Input/Output Device contains two
QuickConnect ports.
Operating Environment 32° F to 104° F (0° to 40° C)
For indoor use only.
ote:N The Room Controller connects to standard GG occupancy sensors, through the OCC-RJ45 Input/Output Device.
Ceiling Sensor Mounting
OAC sensors can be mounted to the ceiling, junction box or round fixture with raceway. Optimum mounting height is 8-10
feet. Do not mount over 12 feet.
Mount at fixture height to avoid obstucting view.
Mount the sensor at least 4-6 feet from air supply ducts to avoid false activation.