EasyManua.ls Logo

Eaton MMX34 Series - Page 121

Eaton MMX34 Series
199 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
04/10 MN04020001Z-EN
Parameter menu (PAR)
117
P12.3 515 - DC braking, start frequency during delay ramp 1.50
0.00 - 10.00 Hz
The output frequency (f
Out
) set here automatically activates the DC
braking after a stop command (FWD/REV switched off).
Requirement: P6.8 = 1 (Stop function ramp).
The output frequency a is reduced after the stop command
according to the deceleration time set at P6.6. Depending on
inertia and the load torque, the speed of the motor b is reduced
accordingly and braked with DC current at the frequency value set
here.
You can set the duration of the DC braking c under P12.4.
PNU ID Access right
RUN
Value Description Factory setting
(P1.3)
f
t
f
out
f
t
P6.6
P6.8 = 1
P12.4
P12.3
FWD
REV
a
b
c

Table of Contents

Other manuals for Eaton MMX34 Series

Related product manuals