Appendix
04/10 MN04020001Z-EN
176
List of parameters
The abbreviations used in the parameter lists have the following 
meaning:
Quick configuration (basis)
The quick-start assistant can be switched off in the first parameter 
(P1.1) by entering a zero (access to all parameters).
In parameter P1.2, you can switch to the specified application 
setting with the quick-start assistant (see table 4, page 44).
The quick-start assistant ends this first cycle by automatically 
switching to frequency display (M1.1 = 0.00 Hz).
By selecting the parameter level (PAR) again, besides the selected 
parameters for the quick-configuration, the system parameters (S) 
are also shown in other cycles.
PNU Parameter number
ID Identification number of the parameter
RUN Access rights to the parameters during operation 
(RUN): / = Modification permissible,
- = Modification only possible in STOP 
ro/rw Parameter read and write permissions via a fieldbus 
connection (BUS)
ro = read only
rw = read and write
DS Factory setting of the parameters
User 
setting
User setting of the parameters
h
When first switching on or after activating the default 
settings (S4.2 = 1), you are guided step by step through 
the provided parameters by the quick-start assistant. The 
defined values are confirmed with the OK button or they 
can be changed to suit your application and the motor 
data.
PNU ID Access right Designation Value range Page FS
(P1.3)
User 
setting
RUN ro/rw
P1.1 115
/
rw Parameter conceal 0 = All parameters
1 = Only quick configuration parameters
73 1
P1.2 540 - rw Drive Setup 0 = Basic
1 = Pump drive
2 = Fan drive
3 = Hoisting device (high load)
73 0
P1.3
1472 - rw Country specific default 
settings (FS)
0 = EU
1 = USA
73 0
P6.1
125 / rw Control place 1 1 = Control signal terminals (I/O)
2 = Control unit (KEYPAD)
3 = Field bus (BUS)
88 3
P6.2
117 / rw Setpoint input 0 = Fixed frequency (FF0)
1 = Control unit (KEYPAD)
2 = Fieldbus (BUS)
3 = AI1 (analog setpoint 1)
4 = AI2 (analog setpoint 2)
5 = Motor potentiometer
88 3
P6.3
101 - rw Minimum frequency 0.00 - P6.4 Hz 89 0.00
P6.4
102 - rw Maximum frequency P6.3 - 320.00 Hz 89 50.00
60.00
P6.5 103 - rw Acceleration time (acc1) 0.1 - 3000 s 89 3.0
P6.6 104 - rw Deceleration time (dec1) 0.1 - 3000 s 89 3.0
P6.7
505 - rw Start function 0 = Acceleration time (ramp)
1 = Flying restart circuit
90 0
P6.8
506 - rw Stop function 0 = Fee coasting
1 = Deceleration time (ramp)
90 0
P7.1 113 - rw Motor, rated operational 
current
0.2 x I
e
-2xI
e
(h Motor rating plate)
94 I
e
P7.3 112 - rw Motor, rated speed 300 - 20000 min
-1
(h Motor rating plate)
94 1440