Parameters
04/10 MN04020001Z-EN
126
The following examples show two practical applications for the 
second parameter set.
Example 1
Roller conveyor with rotary table:
• Motor M1 (0.75 kW) drives the rollers on the rotary table and 
transports the goods further.
• Motor M2 (1.5 kW) rotates the table for the alternating 
acceptance of goods from two feed lines.
For alternating operation (rotary movement “exclusive or” of the 
transport rollers) on the rotary table, a frequency inverter for the 
largest connected load (MMX34AA4D3…) was selected.
The different rating data of the motors were set in the parameter 
groups P7 (for motor M1) and P14 (for motor M2). The second 
parameter set (P14) is activated here as an example via digital 
input DI6 (P3.27 = 6).
The change between the two motors is implemented in this 
example via contactors Q11 (M1) and Q12 (M2) at standstill. The 
enabling and selection of the relevant parameter group is 
activated via the digital inputs:
• Motor M1 = DI1 (FWD, control signal terminal 8) operation 
with parameter group P7.
• Motor M2 = DI1 (FWD, control signal terminal 8) and DI6 (2PS, 
control signal terminal 16) operation with parameter group P14 
(second parameter set).
During maintenance and setting work the following applies for 
reversing duty:
• Motor M1 = DI2 (REV, control signal terminal 9) operation with 
parameter group P7.
• Motor M2 = DI2 (REV, control signal terminal 9) and DI6 (2PS, 
control signal terminal 16) operation with parameter group P14 
(second parameter set).
Figure 103:  Roller conveyor with rotary table
Q11
F1
M1
Q12
F2
M2
U1 V1 W1 U1 V1 W1
M
3
˜
M
0.75 kW 1.5 kW
3
˜
89
DI1
DI2
DI6
16
FWD
REV
2PS
24 V
6
< 50 mA
+24 V Out
h
Digital input DI6 is assigned in the factory setting 
(P3.12 = 6) with the function PI-OFF (PID controller, 
deactivated). Setting P3.12 = 0 is used to switch off this 
function of DI6. Setting P3.27 = 6 enables the second 
parameter set (2PS) function to be assigned to digital 
input DI6.