04/10 MN04020001Z-EN
List of parameters
189
Second parameter set
P14.1
1347 - rw Motor (2PS),
rated current limit
0.2 x I
e
-2xI
e
(h Motor rating plate)
124 I
e
P14.2 1352 - rw Current (2PS) 0.2 x I
e
-2xI
e
124 1.5 x I
e
P14.3 1350 - rw Motor (2PS) nominal speed 300 20000 min
-1
(h Motor rating plate)
124 1440
1720
P14.4
1351 - rw Motor (2PS),
power factor (cos v)
0.30 - 1.00
(
h Motor rating plate)
124 0.85
P14.5
1348 - rw Motor (2PS),
rated voltage
180 - 500 V
(
h Motor rating plate)
124 230
400
P14.6
1349 - rw Motor (2PS), nominal
frequency
30 - 320 Hz
(h Motor rating plate)
124 50.00
60.00
P14.7
1343 - rw Minimum frequency (2PS) 0.00 - P14.8 Hz 124 0.00
P14.8
1344 - rw Maximum frequency (2PS) P14.7 - 320.00 Hz 124 50.00
60.00
P14.9
1345 - rw Acceleration time (acc3) 0.1 - 3000 s 124 3.0
P14.10
1346 - rw Deceleration time (dec3) 0.1 - 3000 s 124 3.0
P14.11
1355 - rw U/f characteristic curve
[2PS]
0 = Linear
1 = Quadratic
2 = Configurable
124 0
P14.12
1354 - rw Torque increase (2PS) 0 = Deactivated
1=activated
125 0
P14.13
1353 - rw Motor (2PS),
temperature protection
0 = Deactivated
1 = Warning
2 = Error, stop according to P6.8
125 0
P14.14
1469 - rw Motor (2PS),
ambient temperature
-20 - +100 °C 125 40
P14.15
1470 - rw Motor (2PS),
cooling factor at zero
frequency
0.0 - 150 % 125 40.0
P14.16
1471 - rw Motor (2PS),
thermal time constant
1 - 200 min 125 45
PNU
ID Access right Designation Value range Page FS
(P1.3)
User
setting
RUN ro/rw