Instruction Leaflet IL01906008E
Effective March 2011
Instructions for Testing Magnum DS
Digitrips with the MTK2000 Test Kit
EATON CORPORATION www.eaton.com
Breaker
Closed?
SELECT TEST:
> LONG DELAY TEST
Timer
Expired?
N
Y
Y
N
Test Select or
Down Arrow
G H
Down Arrow
(Dec ‘r’ Value)
Up Arrow
(Inc ‘r’ Value)
D
Cancel
Button?
Cancel
Y
N
1. SET SD&GF PICKUP MAX
2. SET INST TO OFF
(Informational)
Start
E
SET LDS; START: ADJ PU
>r=X.XX n=XXXX Ir=XXXX
Start
Test Select
or Cancel
Cancel
LONG DELAY TIME MULT
>mult=XX.X LDT @ multxIr
Up Arrow
(Inc ‘m’ Value)
Down Arrow
(Dec ‘m’ Value)
LONG DELAY T(S) @6.0xIr
>Tr=XX mult= X.X LDT=X.XX
Up Arrow
(Inc ‘Tr’ Value)
Down Arrow
(Dec ‘Tr’ Value)
Cancel
Test Select
or Cancel
NOTE: Values will wrap at range
limits when incrementing &
decrementing with Arrow buttons.
Test Select
Start or
Test Select
Start
<NAME> = LONG
<NAME> DELAY RUNNING
I=XX T=X.XXS
(Test Running)
Within
Time
Limits
TEST
SCENARIO
Cancel
Test
Failed
Test
Passed
N
Y
SYSTEM STOPPING
<NAME> DELAY CANCELLED
>I=XXX T=X.XXS R=XXXS
<NAME> DELAY **FAILED**
>I=XXX T=X.XXS R=XXXS
<NAME> DELAY **PASSED**
>I=XXX T=X.XXS R=XXXS
Cancel
Test
Failed
Test
Passed
2 Second
Timeout
15 Second
Timeout
15 Second
Timeout
15 Second
Timeout
Time Test
Return
Time Test
Entry
<NAME>
Assigned
From Entry
Point
NOTE: Lower Time
limit modified by ZSI
parameter. See Charts.
F
PU Test
Entry
Start
PU Test
Return

Questions and Answers: