8
Instruction Leaflet IL01906008E
Effective March 2011
Instructions for Testing Magnum DS
Digitrips with the MTK2000 Test Kit
EATON CORPORATION www.eaton.com
4.15 Maintenance Mode Setting
4.15.1 MDS520 Digitrip Models
If any of the red LEDs are blinking press “Reset” on Digitrip.
Set Maintenance Mode dial “On”
Set R value on the dial below the Maintenance Mode “On” Dial.
Set value on the Long Delay dial to maximum.
Set value on the Long Delay Time dial to maximum.
Set value on the Short Delay Setting dial to maximum.
4.15.2 MTK2000
Press Test Select until “MAINTENANCE MODE TEST” comes up on
the MTK2000. Press Start.
The MTK2000 display is specifying that values need to be set, these
values were set in the Digitrip Instructions. Press Start.
Set the “R” value on the MTK2000 display to match the Digitrip’s
Maintenance Mode R values by scrolling the up and down arrows.
ote:N If you are not sure which R value is needed the next menu will allow
the multiplier value to be set.
Press Test Select for “MMODE TRIP SET” menu, the “mm” value
can be adjusted up or down to give you the R value desired for test-
ing.
Once value is set press Start on MTK2000.
A message of “TRIP CURRENT FOUND –> PASSED” or “TRIP
CURRENT FOUND –> FAILED” will appear on the MTK2000 display.
4.16 Maintenance Mode Time Settings
4.16.1 MDS 520 Digitrip Models
If any of the red LEDs are blinking on Digitrip press Reset.
4.16.2 MTK2000
After the “MAINTENANCE MODE” current is found press Test
Select until “MMODE MAX TIME” comes up on the MTK2000 dis-
play.
ote:N If Test Select is hit more than twice, the MTK will skip the next test
sequence. The only way to return to the time test is to redo the Im current
test.
Press Start and the MTK2000 will return the Maintenance Mode trip
time.
A message of “MAINTENANCE PASSED” or “MAINTENANCE
FAILED” will appear on the MTK2000 display.
If test is failing please reference Section 2.3 MTK2000 Breaker
Cables.
Section 5: Testing the 1150 Digitrip Models
5.1 Legend for MTK2000 testing with 1150 Digitrips
g= entered ground value setting
GF= GND PU
i(A)= the entered instantaneous value setting
l(A)= the output current value for the MTK2000 tested
I
g
(A)=
I
n
x g
l
i
(A)= l
n
x i
l
m
(A)= l
r
x m
l
mult
(A)= l
r
x mult
I
n
(A)
= rated plug value (must match sensor rating, I
s
)
I
r
= (A) l
n
x r
I
s
(A)= l
r
x s
INST= INST PU
LDS= LONG PU
LDT= LongTIME
mm= limit for Maintenance mode reduction levels
mult= multiplying factor
MMODE= Maintenance Mode
n= Rating Plug Value
r= Long PU
R= the actual time the Digitrip tripped during the test
s= SHORT PU
SDS or SD= SHORT PU
SDT= SHORT TIME
T= is the entered time value the MTK2000 started a time test at
T
g
= entered time value for the “GROUND TIME”
T
r
= entered time value for the “LongTIME”
T
s
= entered time value for the “SHORT TIME”
5.2 Entering Breaker Name
The MTK2000 is capable of storing test results as each test is per-
formed. For this reason, it is important to label the breakers subject
to test in the MTK2000 memory. When prompted for breaker name
on the display screen press Start then use the Up Arrow and Down
Arrow to change the character and Start button to advance to the
next character. The Cancel button can be pressed to move to the
previous field. The Phase Select button, when pressed, performs
the delete function. Once the entry is complete, press the Test
Select button to proceed.
It is important to press the Cancel button twice to return to the
Home Screen after performing all tests on one breaker before pro-
ceeding to the next breaker so that a new breaker name can be
entered.

Questions and Answers: