Step 1 — Wiring (Continued)
Hazardous High Voltage, continued 
Basic Wiring Diagram
Users must connect wiring according to the following circuit diagram.
Control Terminal Wiring (Factory Settings)
Terminal Symbols
Note: Use twisted-shielded, twisted-pair or shielded-lead wires for the control 
signal wiring. It is recommended to run all signal wiring in a separate steel 
conduit. The shield wire should only be connected at the drive. Do not connect 
shield wire on both ends. 
Catalog Number
Voltage 
Horsepower
Max. Current (A)
(Input/Output)
Wire
Gauge
(AWG)
Torque
Rating
(kgf-cm)
MVX001A0-5
MVX002A0-5
MVX003A0-5
575V AC, 1 hp
575V AC, 2 hp
575V AC, 3 hp
1.7A/2.4A
3.0A/4.2A
4.2A/5.9A
12 – 14
12 – 14
12 – 14
14
MVX005A0-5
MVX007A0-5
MVX010A0-5
575V AC, 5 hp
575V AC, 7-1/2 hp
575V AC, 10 hp
6.6A/7.0A
9.9A/10.5A
12.2A/12.9A
8 – 14
8 – 14
8 – 12
15
Terminal 
Symbols Terminal Name Remarks
R01 - R02 Digital Output Relay Refer to 40.04 Relay output contact
RO1 - RO2 (NC Contact)
RO3 - RO2 (NO Contact)
R03 - R02 Digital Output Relay
D01 - DCM Digital photocouple output Refer to 40.03
RJ-12 Serial communication port RS-485 serial communication interface
+10V - COM Power Supply (+10V)
AI1 - COM
AI2 - COM
Analog voltage input
Analog current input
0 to +10V Input
0 to 20 mA or 4 to 20 mA Input
AO+ - COM Analog frequency/current 
meter
0 to +10V Output
DI1 - COM Digital input 1 Refer to 30.11
DI1 - COM
to
DI6 - GND
Digital input 1
to
Digital input 6
HIGH VOLTAGE!
Wiring work shall be carried out only by qualified personnel. 
Otherwise, there is a danger of electric shock or fire.
NO
Relay Output
Factory Setting
   Bias 
Potentiometer
Full scale voltmeter
0 to 10V DC
Factory Setting:
Output Frequency
Factory Setting:
Inverter Running
Digital Output
Run/Stop
Reverse/Forward
Preset Speed 1
Preset Speed 2
Preset Speed 3
Reset
RO3 RO2 RO1
DI1 DI2
DI3
DI4
DI5
DI6
COM
AO+
AI1
+10V
AI2
COM
DO1 DOC
NC Relay Output
4–20 mA
 