Step 4 — Parameter Groups & Default Values
Parameter
G
roups
The parameters are grouped according to the following descriptions:
10 Reserved (and not displayed)
20 Basic Grouping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
30 Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
40 Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
50 Drive Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
60 Motor Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
70 Protective Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
80 Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
90 Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
MVX9000 Parameter Listing
20 — BASIC GROUPING (Quick Start)
Modbus Groups Description Range Default
User
Settings
0000H 20.01
50.05
Motor Nameplate
Frequency
10.0 to 400.0 Hz 60.0
0001H 20.02
50.06
Motor Nameplate
Voltage
115/230V drives: 1.0 to 255V 230
460V drives: 1.0 to 510V 460
575V drives: 1.0 to 637V 575
0002H 20.03
50.01
Source of Master
Frequency
00: Master frequency determined by
digital keypad up/down
01
01: Master frequency determined by
keypad potentiometer
02: Master frequency determined by
0 to +10V input on AI terminal
03: Master frequency determined by
4 to 20 mA input on AI terminal
04: Master frequency determined by
RS-485 communication interface
0003H 20.04
50.02
Source of Operation
command
00: Operation commands
determined by digital keypad
00
01: Operation commands
determined by external control
terminals, keypad STOP is effective
02: Operation commands
determined by external control
terminals, keypad STOP is
ineffective
03: Operation commands
determined by RS-485 interface,
keypad STOP is effective
04: Operation commands
determined by RS-485 interface,
keypad STOP is ineffective
0004H 20.05
60.01
Motor Rated Current 30 to 120% FLA
0005H 20.06
50.09
Minimum Output
Frequency
0.0 to 20.0 Hz 1.5
0006H 20.07
50.04
Maximum Output
Frequency
50.0 to 400.0 Hz 60.0
0007H 20.08
50.12
Acceleration Time 1 0.01 to 600.0 sec 10.0
0008H 20.09
50.13
Deceleration Time 1 0.01 to 600.0 sec 10.0