NZM-XDMI-DPV1
(PROFIBUS-DPV1 Interface for
DMI)
140
11/04 MN01219002Z-EN
Addressing and length of the object
Please use the following information for addressing of the
object:
• API is equal to 0 (only required for class 2 DPV1 master),
• Slot number is equal to 0,
• The index is equal to 14.
The length of the data to be written is 9 Octets. Please
ensure that you do not enter other lengths when calling the
Write service as otherwise you will receive a fault indication.
Variable definitions (example) for the object
According to IEC 61131-3, you define the following variable
(data module):
h
Parameter values are only accepted from the electronic
control unit when they are less than or equal to the locally
set parameter values.
Name Data type
LS_new_parameters STRUCT
Options ARRAY [1..16] OF BOOL or
ARRAY [1..2] OF BYTE
I
r
BYTE or USINT
I
i
T
r
I
sd
T
sd
I
dn
T
vdn