4 Field Installed UPM Installation
4.1 Preliminary Installation Information
WARNING
Installation should be performed only by qualified personnel.
Refer to the following while installing the Field Installed UPM (FI-UPM):
Chapter 3 for cabinet dimensions, equipment weight, wiring and terminal data, and installation
notes.
Do not tilt the cabinet more than 10° during installation.
The FI-UPM cabinet is installed on the left side of the UPS cabinet.
The FI-UPM cabinet is shipped with a debris shield covering the ventilation grill on top of the unit.
Do not remove the debris shield until installation is complete. However, remove the shield before
operating the UPS system. Once the debris shield is removed, do not place objects on the
ventilation grill.
A FI-UPM is always designated as UPM 4.
4.2 Unloading the FI-UPM Cabinet from the Pallet
The FI-UPM cabinet is bolted to a wooden pallet supported by wood skids. To remove the pallet:
WARNING
The FI-UPM cabinet is heavy (see Table 3-1 on page 8). If unpacking and unloading instructions
are not closely followed, the cabinet may tip and cause serious injury.
CAUTION
Do not tilt cabinets more than 10° from vertical.
Lift the cabinet only with a forklift or damage may occur.
NOTE
For the following steps, verify that the forklift or pallet jack is rated to handle the weight of the
cabinet (see Table 3-1 on page 8 for cabinet weight).