Figure 4-2. Removing the Right Side Shipping Bracket
4.3 Mechanical Installation
To mechanically install the FI-UPM:
1. Remove the wire entry plate located on the bottom left side of the UPS cabinet (see Figure 4-3).
2. If not already removed, remove the wire entry knockout located on the top left side of the UPS
cabinet (see Figure 4-3).
3. Locate the hardware kit (packed inside of the cabinet). Locate the nylon grommet from the
hardware kit. If not already installed, install the nylon grommet in the knockout hole.
4. Using a forklift, move the FI-UPM cabinet to the final installed location on the left side of the UPS
cabinet. Verify that the FI-UPM cabinet right side is against the UPS cabinet left side and the front
panels are flush with each other.
5. Carefully lower the FI-UPM cabinet until the cabinet base contacts the floor.
1FI-UPM Removable Front Panel
2Pallet
3 Right Side Shipping Bracket
4Shipping Bracket Bolts