EasyManua.ls Logo

Eaton Powerware 9355 - Battery Specifications; Battery Runtimes

Eaton Powerware 9355
120 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SPECIFICATIONS
Eaton 9355 UPS (10/15 kVA) User's Guide S 164201594 Rev D www.eaton.com/powerquality
103
Table 15. Battery Specifications
Battery Type 9 Ah sealed, valve-regulated lead acid (VRLA), maintenance-free, minimum 3-year float
service life at 25°C (77°F), voltage 192 Vdc (96 cells per string)
Number of Strings Maximum of 22 strings per full configuration, including UPS batteries
(4 EBM-64 cabinets or 3 EBM-96 cabinets, plus UPS batteries)
UPS-32: 2 strings; UPS-64: 4 strings
EBM-64: 4 strings; EBM-96: 6 strings
Battery Replacement Must be replaced by a qualified service technician
Charger Service configurable 0.5–34A per string, with overall maximum of 34A (limited by input
current). Default: 3.4A per string
Charging Internal battery: approximately 3 hours to 80% usable capacity at nominal line voltage
after full load discharge
External battery: no more than 10x discharge time to 90% usable capacity at nominal
line voltage after full load discharge
Start-on-Battery Allows start of UPS without utility input
Performance ABM technology increases battery service life, optimizes recharge time, and provides a
warning before the end of useful battery life
Protection Extended Battery Module output protected by 100A circuit breaker
Table 16. Battery Runtimes (in Minutes) at Full Load
2-High Cabinets
Load
32 Internal UPS
Batteries
(1) EBM-64 (2) EBM-64 (3) EBM-64 (4) EBM-64
15 kVA/13.5 kW 4 23 43 65 88
10 kVA/9 kW 8 37 69 106 144
3-High Cabinets
Load
64 Internal UPS
Batteries
(1) EBM-96 (2) EBM-96 (3) EBM-96
15 kVA/13.5 kW 13 43 76 113
10 kVA/9 kW 22 69 124 184
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.

Table of Contents

Other manuals for Eaton Powerware 9355

Related product manuals