6. To check the operation of the RMP, ensure that the UPS is
supplying the load via the inverter or bypass. If the indicators on the
RMP show the appropriate status, then it is operating correctly.
If the RMP is not operating correctly, check the wiring, the fuse on
the IRC, and the plug‐in terminal blocks for proper seating. If all
connections are secure but the RMP still does not operate correctly,
replace the fuse. If this does not correct the problem, contact your
service representative for verification that the RMP is working
correctly.
Plug-in Terminal Block J1
to Industrial Relay Card
NOTE Conduit and wiring
supplied by the customer. The
maximum distance between
the RMP and the UPS is not to
exceed 152.4m (500 ft).
Figure 55. RMP Top Internal View